NETWORK VARIABLES
6.6.2 PID measured value (network input SNVT_lev_percent nviInvPIDValue)
Enter the measured value of air volume, temperature, etc. in 0.005% increments.
Data acceptance timing........... At network variable receive (nv_update_occurs event)
For example, when the measured value is 25°C on a 10°C/0% and 50°C/100% detector,
As the PID measured value, input 37.50%.
Data Name Initial Value Range Increments
nviInvPIDValue 0.000% 0.00% to 100.00% 0.005%/bit
REMARKS
Control cannot be exercised at less than the minimum resolution (0.01%) of the inverter.
When the value outside of the range is input, the input value is made invalid and the inverter operates with the value
set last time.
(50 - 10)
(25 - 10)
× 100 = 37.5%.