Instruction manual

72
NETWORK VARIABLES
6.7 Inverter Extended Functions
6.7.1 Monitor code (network input SNVT_count nviInvMonCode)
Set the monitor data you want to monitor.
The monitor value enters "monitor data (nvoInvMonData)" (Refer to page 75).
Data acceptance timing........... At network variable receive (nv_update_occurs event)
<Monitor Code Table>
When a monitor code other than the below is set, monitor data (nvoInvMonData) becomes arbitrary value.
Data Name Initial Value Range Increments
nviInvMonCode H0 H0 to H0036
Code
Number
Description
Increments
100% Value of Event Driven Detection Width (Refer to page
102)
H0000 No monitoring
*1 
H0001 Output frequency 0.01Hz Pr. 55 Frequency monitoring reference setting
H0002 Output current 0.01A Pr. 56 Current monitoring reference setting
H0003 Output voltage 0.1V 200V class: 400V, 400V class: 800V
H0004 No monitoring
*1 
H0005 Frequency setting 0.01Hz Pr. 55 Frequency monitoring reference setting
H0006 No monitoring
*1 
H0007 Motor torque 0.1% Rated torque of the applied motor × 2
H0008 Converter output voltage 0.1V 200V class: 400V, 400V class: 800V
H0009 Regenerative brake duty 0.1% Pr.70 Special regenerative brake duty setting
H000A
Electronic thermal relay function
load factor
0.1% 100%