NETWORK VARIABLES
6.7.3 Set frequency (0.01Hz increments) (network input SNVT_count
nviInvSetFreq2)
You can set the set frequency in 0.01Hz increments.
Data acceptance timing........... At network variable receive (nv_update_occurs event)
For example, if you want to set 120.00Hz, set "12000", the value 100 times greater than the desired
frequency.
6.7.4
Output frequency monitor (0.01Hz increments) (network output SNVT_count
nvo
I
nvOutFreq2)
You can monitor the output frequency of the inverter in 0.01Hz increments.
Data send event ......................When the data changes in 0.01Hz increments
Data send timing ..................... As set in Pr. 388 Send time interval at heart beat and Pr. 389 Minimum sending
time at heart beat. (Refer to page 87)
For example, if the monitor value is 120.00Hz, "12000", the value 100 times greater, is displayed.
Data Name Initial Value Range Increments
nviInvSetFreq2 0.00Hz 0.00Hz to 400.00Hz 0.01Hz/bit
REMARKS
Always set frequency (Hz) regardless of the Pr.37 setting.
Data Name Initial Value Range Increments
nvoInvOutFreq2 0.00Hz 0.00Hz to 400.00Hz 0.01Hz/bit
REMARKS
It is always displayed as frequency (Hz) regardless of the Pr.37 setting.