Instruction manual

90
NETWORK VARIABLES
6.8.8 Acceleration time (network input config SNVT_time_sec
nciRampUpTm)
You can set the acceleration time taken for the motor to reach the set frequency (1 to 400Hz) of Pr. 20
Acceleration/deceleration reference frequency from 0Hz.
* The setting range changes according to the Pr. 21 Acceleration/deceleration time increments setting. The value 0.1 times greater than
the setting value is written to the inverter when Pr. 21 = 1. When the Pr. 21 setting has been changed, set the acceleration time again.
(Example)
When Pr. 21 = "0", setting "5.0s" for acceleration time and "1" in Pr. 21 automatically changes the acceleration time setting to "0.5s".
Data acceptance timing........... At network variable receive (nv_update_occurs event)
Data Name Initial Value Range * Increments
Setting Value
Storage Location
Pr.21 Setting
nciRampUpTm Initial value of Pr. 7
0 (Initial value) 0.0s to 3600.0s 0.1s/bit
Pr. 7
1 0.00s to 360.00s 0.01s/bit
REMARKS
Refer to the inverter manual for details of Pr. 7, Pr. 20, Pr. 21.