When a protective function is activated,
the output of the inverter is switched off.
The motor runs until stop. The output
remains switched off until the error cause
is eliminated and the inverter is reset.
The inverter can be reset following four
different methods:
Switch the power supply OFF and ON
again.
Switch the reset signal ON for at least
0.1 s and switch it OFF again.
Press the RESET key on the control
panel.
Menu-guided reset via the optional
parameter unit FR-PU04
If the reset signal is ON continuously, the
control panel FR-PA02-02 returns an error
message while the control unit FR-PU04
indicates that the reset procedure is in
progress.
When a protective function is activated,
the control panel FR-PA02-02 returns an
error code as listed in the table above.
The parameter unit FR-PU04 indicates a
more detailed error message.
If an error occures and the input protection
contactor is toggled the error message can-
not be retained, since there is no power
supply for the control circuit.
Activating a protective function and resetting methods
Display on
control panel
FR-PA02-02
Meaning Description Remedy
E.CPU
CPU error Scan time of CPU was exceeded. Failure on CPU printed circuit board.
Restart the inverter.
Contact the customer service if the error
occurs again.
E. 3
Fault 3 (option error) The dedicated option used in the inverter results in setting error or connection fault.
Check the function setting of the option board.
Check that the communication option is plugged
in the connector securely
E. 6
Fault 6 (CPU error)
This functions stops the inverter output if a communication error occurs in the built-in CPU.
Please contact your nearest MITSUBISHI
ELECTRIC representative if the error occurs
repeatedly.
E. 7
Fault 7 (CPU error)
E.LF
Open output phase
protection
One of the phases (U, V, W) is not connected. Check the connections.
E.P24
Shortcut at 24 V DC A shortcut at the 24 V output has occured (PC terminal). Remove the shortcut!
PS
Inverter was stopped via
control panel
STOP key on the control panel was pressed during external operating mode. Check parameter 75.
OL
Motor run under overload?
Sudden deceleration?
oL: Overvoltage
OL: Overcurrent
The load is too large or the brake frequency is too high. Reduce the load or the brake frequency.
Err
Error CPU error has occured.
Please contact your nearest MITSUBISHI
ELECTRIC representative if the error occurs
repeatedly.
READ
INV.Reset
Exec.<WRITE>
Cancel <ESC>
5AlarmHist.
6 Alarm Clear
7 Inv. Reset
8 T/Shooting
Menu-guided reset with FR-PU04