Specifications

24
MITSUBISHI ELECTRIC
FR-E 500 EC
Noise Filters for FR-E 540/520
Noise filters
For complying with the EMC directives of
the European Community regarding the
electromagnetic campatibility, the FR-E
500 EC inverter has to be equipped with
a noise filter across the input circuit.
Additionally it has to be installed and
wired according to the EMC directives.
The filters are designed to reduce con
-
ducted noise voltages to comply with the
limits defined for Environments 1 and 2.
To ensure a proper and safe operation of
the components follow the points below:
Ground the filter prior to applying the
power supply.
For the selection of a ground fault pro
-
tective switch or relay take the leakage
current of the filter into account.
Ensure a perfect grounding of the filter,
if you do not intend to use a protective
switch or relay across the input circuit.
Filter
Inverter
Power
loss [W]
Leakage
current [mA]
Weight
[kg]
Art. no.
FR-E 520S EC FR-E 540 EC
FFR-E540-4.5A-SF1 0.4 k–0.75 k
4 < 30 1.3 126654
FFR-E540-15A-SF1 1.5 k–3.7 k
12 < 30 1.45 126655
FFR-E540-27A-SF1 5.5 k–7.5 k
25 < 30 1.7 126656
FFR-E520S-14A-SC1 0.4 k – 0.75 k
11 < 30 1.3 152727
FFR-E520S-26A-SC1 1.5 k – 2.2 k
17 < 30 1.3 152730
The filters can provide conformity with the limits for Environment 1 (unrestricted distribution) with motor cable lengths of up to 20m
(shielded) and for Environment 1 (restricted distribution) with motor cable lengths of up to 100m (shielded), and thus also with the 100A
limits of Environment 2 with motor cable lengths of up to 100m.
Type SF-1
Built-on filter SC1
Input Reactors for Three-Phase Current FR-BAL-B-첸첸k
Three-phase input reactors
Thethree-phaseinputreactors
FR-BAL-B-첸첸kforthefrequency
inverters FR-E 540 EC compensate
voltage fluctuations and simultaneously
increase the efficiency.
Applying the appropriate input reactors
an overall efficiency of up to 90 % can be
achieved.
The use of an input reactor is especially
recommended for main circuits where high
capacities are switched, for example, via
thyristors.
Inverter Input reactors Power capacity L [mH] Current [A] Power loss [W] Insulation class Weight [kg] Art. no.
FR-E 540 EC
FR-BAL-B-4.0 k FR-E 540-0.4 k – 4.0 k
2.340 12 31 T40/E 3.0 87244
FR-BAL-B-5.5k FR-E 540-5.5 k
1.750 16 44 T40/E 3.7 87245
FR-BAL-B-7.5 k FR-E 540-7.5 k
1.220 23 59 T40/E 5.5 87246
OPTIONS
FFR-E540-4,5A-SF1
Fs5710 - 4,5 - 0,7
LOAD
LINE
MEU-MAT-NO.
126654
3x480VAC/50- 60Hz
4,5A@50°C /25/085/ 21
SCHAFFNER