Main circuit terminal specifications
NOTE
y Especially for long-distance wiring, the inverter may be affected by a charging current caused by the stray
capacitances of the wiring, leading to a malfunction of the overcurrent protective function, fast response current limit
function, or stall prevention function or a malfunction or fault of the equipment connected on the inverter output side.
If fast-response current limit malfunctions, disable this function. When the stall prevention function misoperates,
increase the stall level. ( Refer to Pr. 22 Stall prevention operation level and Pr. 156 Stall prevention operation selection in
the chater 4 of the Instruction Manual)
y Refer to the chater 4 of the Instrunction Manual for details of Pr. 72 PWM frequency selection . Refer to the manual of the
option for details of surge voltage suppression filter (FR-ASF-H/FR-BMF-H).
y When using the automatic restart after instantaneous power failure function with wiring length exceeding below,
select without frequency search (Pr. 162 = "1, 11"). (
Refer to the chater 4 of the Instruction Manual)
Motor capacity
(kW(HP))
0.1(1/8) 0.2(1/4) 0.4(1/2)
Wiring length 20m(65.61feet) 50m(164.04feet) 100m(323.08feet)