Instruction manual

14
PARAMETER LIST
52
DU/PU main display data
selection
0, 5, 7 to 12,
14, 20, 23 to
25, 52 to 57,
61, 62, 100
0
55
Frequency monitoring
reference
0 to 400Hz 60Hz
56 Current monitoring reference 0 to 500A
Rated
inverter
current
57 Restart coasting time
0, 0.1 to 5s,
9999
9999
58 Restart cushion time 0 to 60s 1s
59 Remote function selection 0, 1, 2, 3 0
60
Energy saving control
selection
0, 9 0
61 Reference current
0 to 500A,
9999
9999
62
Reference value at
acceleration
0 to 200%,
9999
9999
63
Reference value at
deceleration
0 to 200%,
9999
9999
65 Retry selection 0 to 5 0
66
Stall prevention operation
reduction starting frequency
0 to 400Hz 60Hz
67
Number of retries at fault
occurrence
0 to 10, 101
to 110
0
68 Retry waiting time 0.1 to 360s 1s
69 Retry count display erase 0 0
70
Special regenerative brake
duty
0 to 30% 0%
71 Applied motor
0, 1, 3 to 6,
13 to 16, 23,
24, 40, 43,
44, 50, 53,
54
0
72 PWM frequency selection 0 to 15 1
73 Analog input selection 0, 1, 10, 11 1
74 Input filter time constant 0 to 8 1
75
Reset selection/disconnected
PU detection/PU stop
selection
0 to 3, 14 to
17
14
77 Parameter write selection 0, 1, 2 0
78
Reverse rotation prevention
selection
0, 1, 2 0
79 Operation mode selection
0, 1, 2, 3, 4,
6, 7
0
80 Motor capacity
0.1 to 15kW,
9999
9999
81 Number of motor poles
2, 4, 6, 8, 10,
9999
9999
82 Motor excitation current
0 to 500A,
9999
∗4
9999
83 Motor rated voltage 0 to 1000V
200V/
400V
∗6
84 Rated motor frequency 10 to 120Hz 60Hz
Parameter
Name
Setting
Range
Initial
Value
89
Speed control gain (advanced
magnetic flux vector)
0 to 200%,
9999
9999
90 Motor constant (R1)
0 to 50,
9999
∗4
9999
91 Motor constant (R2)
0 to 50,
9999
∗4
9999
92 Motor constant (L1)
0 to 1000mH,
9999
∗4
9999
93 Motor constant (L2)
0 to 1000mH,
9999
∗4
9999
94 Motor constant (X)
0 to 100%,
9999
∗4
9999
96 Auto tuning setting/status 0, 1, 11, 21 0
117
PU communication station
number
0 to 31 (0 to
247)
0
118 PU communication speed
48, 96, 192,
384
192
119
PU communication stop bit
length
0, 1, 10, 11 1
120
PU communication parity
check
0, 1, 2 2
121
Number of PU communication
retries
0 to 10, 9999 1
122
PU communication check time
interval
0, 0.1 to
999.8s,
9999
0
123
PU communication waiting
time setting
0 to 150ms,
9999
9999
124
PU communication CR/LF
selection
0, 1, 2 1
125
Terminal 2 frequency setting
gain frequency
0 to 400Hz 60Hz
126
Terminal 4 frequency setting
gain frequency
0 to 400Hz 60Hz
127
PID control automatic
switchover frequency
0 to 400Hz,
9999
9999
128 PID action selection
0, 20, 21, 40
to 43, 50, 51,
60, 61
0
129 PID proportional band
0.1 to
1000%, 9999
100%
130 PID integral time
0.1 to 3600s,
9999
1s
131 PID upper limit
0 to 100%,
9999
9999
132 PID lower limit
0 to 100%,
9999
9999
133 PID action set point
0 to 100%,
9999
9999
134 PID differential time
0.01 to
10.00s, 9999
9999
145 PU display language selection 0 to 7 1
146 Parameter for manufacturer setting. Do not set.
147
Acceleration/deceleration time
switching frequency
0 to 400Hz,
9999
9999
150 Output current detection level 0 to 200% 150%
151
Output current detection signal
delay time
0 to 10s 0s
152 Zero current detection level 0 to 200% 5%
153 Zero current detection time 0 to 1s 0.5s
Parameter
Name
Setting
Range
Initial
Value
E700_NA_Guideline_ib0600333ENG.book 14 ページ 2007年11月28日 水曜日 午前10時20分