yTo use the inverter outside of an enclosure in the environment of pollution degree 2, fix a fan cover with fan cover fixing
screws enclosed.
On the input and output of the inverter, use cables of the type and size set forth in EN60204 Appendix C.
The operating capacity of the relay outputs (terminal symbols A, B, C) should be 30VDC, 0.3A. (Relay outputs are
basically isolated from the inverter internal circuit.)
Control circuit terminals on page 4 are safely isolated from the main circuit.
Environment
FR-E720-175 or less
FR-E740-095 or less
Example for FR-E740-095
FR-E720-240 or more
FR-E740-120 or more
Example for FR-E740-120
Running In Storage During Transportation
Ambient Temperature
-10°C to +50°C
(14°F to 122°F)
-20°C to +65°C
(-4°F to 149°F)
-20°C to +65°C
(-4°F to 149°F)
Humidity 90% RH or less 90% RH or less 90% RH or less
Maximum Altitude
1000m
(3280.80feet)
1000m
(3280.80feet)
10000m
(32808.39feet)
Details are given in the technical information "Low Voltage Directive Conformance Guide" (BCN-A21041-203). Please contact your sales
representative.
Fan connection
connector
Fan
Fan cover
Fan cover
fixing screw
Fan
Fan cover
Fan cover
fixing screws
Fan connection
connector