Instruction manual

2
PRODUCT CHECKING AND PARTS IDENTIFICATION
z General Precaution
The bus capacitor discharge time is 10 minutes. Before starting wiring or inspection, switch power off, wait for more than 10
minutes, and check for residual voltage between terminal P/+ and N/- with a meter etc., to avoid a hazard of electrical shock.
z Environment
Before installation, check that the environment meets following specifications.
Ambient temperature
Temperature: -10°C to +50°C (
14°F to 122°F
)
Ambient humidity 90% RH maximum
Storage temperature -20°C to +65°C
(
-4°F to 149°F) (Temperature applicable for a short time, e.g. in transit.)
Ambience Indoors (free from corrosive gas, flammable gas, oil mist, dust and dirt)
Altitude, vibration
Maximum 1,000m (3280.80feet) above sea level. After that derate by 3% for every extra 500m
(1640.40feet) up to 2500m (8202feet) (92%).
5.9m/s
2
or less
Note
y Install the inverter on a strong surface securely and vertically with bolts.
y Leave enough clearances and take cooling measures.
y Avoid places where the inverter is subjected to direct sunlight, high temperature and high humidity.
y Install the inverter on a non-combustible wall surface.
5cm
(1.97inches)
5cm
(1.97inches
)
5cm
(1.97inches)
Measurement
position
Measurement
position
Inverter