Instruction manual

12
Connection diagram, encoder cable,
PU connector
2.2.3 Encoder connection cable (FR-V5CBL)
When using a dedicated motor (SF-V5RU series), use an encoder cable (FR-V5CBL) for connection.
2.2.4 Setting the encoder
When a dedicated encoder cable (FR-V5CBL) is used, a setting change may not be required.
(1) Setting the power supply specification of the encoder and pulse output type
Switch the position of the jumper connector on the back surface of the control circuit terminal block according
to the encoder specification. (Refer to page 17 for removal and installation of the control circuit terminal block.)
CAUTION
Make setting correctly.
Fitting the jumper connector to the position exceeding the power specification results in an encoder
failure. Fitting the jumper connector to the position below the power specification results in an encoder
malfunction.
L
MS3106B20-29S
Earth (Ground) wire
F-DPEVSB 12P
×
0.2mm
2
MS3057-12A
Encoder side
connector
Inverter side
60
11
(Unit: mm
)
FR-V500 Encoder
Inverter earth (ground) terminal
PZR
PZ
PBR
PB
PAR
PA
SD
PG
G
F
D
C
B
A
R
S
2mm
2
A
B
C
D
E
K
F
G
H
J
L
M
S
N
R
P
T
MS3106B20-29S
(As viewed from wiring side)
Positioning keywa
y
Contact us separately for other lengths.
Type Length L (m) Remarks
FR-V5CBL5 5
Standard productFR-V5CBL15 15
FR-V5CBL30 30
CAUTION
Encoder power supply jumper
connector
The jumper connector is fitted
to 12V when shipped from the
factory. Switch its position
according to power supply
specification.
REMARKS
Since the specification of the encorder
of the conventional motors (SF-VR,
SF-JR with encorder) is 5V, fit the
jumper connector to 5V.
Power supply voltage is 5V
Power supply voltage is 12V
Power supply voltage is 24V
Power supply voltage is external