Instruction manual

21
Setting the motor
INSTALLATION AND WIRING
2
REMARKS
When using a conventional motor (SF-VR, SF-JR) or other motors, refer to the
Instruction Manual (detailed).
<At-a-glance guide to setting the motor>
<When using other manufacturers’ motors>
Offline auto tuning (rotation mode) is necessary. Perform offline auto tuning with the motor alone before connecting
a load. If higher torque accuracy is required, perform online auto tuning next.
No. Item
Parameter,
Jumper
Connector,
Terminal
Description
Dedicated Motor Standard Motor
Constant-torque Motor
(with encoder)
Mitsubishi Mitsubishi
Other
manufacturer
(with
encoder)
Mitsubishi
Other
manufacturer
SF-V5RU
1500r/min
series
SF-VR-
5.5kW to
45kW
SF-JR (with encoder)
SF-HR
(with
encoder)
Others
(with
encoder)
SF-HRCA
(4P) (with
encoder)
SF-JRCA
(with
encoder)
(2, 4, 6P)-
2.2kW to
55kW
(4P)-
1.5kW or
less
1
Motor
setting
Pr. 71 setting
30 30 0 20 3 to 8 3 to 8 3 to 8 10 13 to 18 13 to 18
2
Offline
tuning
Not
required *
Not
required *
Not
required *
Not
required *
Required Required Required
Not
required *
Required Required
3
Capacity
setting
Pr. 80 setting
1 :1
INV
capacity
INV
capacity
INV
capacity
INV
capacity
INV
capacity
INV
capacity
INV
capacity
INV
capacity
INV
capacity
INV
capacity
1 rank
lower
Motor
capacity
Motor
capacity
Motor
capacity
Motor
capacity
Motor
capacity
Motor
capacity
Motor
capacity
Motor
capacity
Motor
capacity
Motor
capacity
4
Number
of
encoder
pulses
Pr. 851setting
2048 1000 1024 1024 1024 (*2) (*2) 1024 1024 (*2)
5
Encoder
rotation
direction
Pr. 852 setting
1 1 1 1 1 (*2) (*2) 1 1(*2)
6
Encoder
power
supply
specification
Encoder
power supply
jumper
connector on
the back of
the control
terminal
Power
supply
specification
12V5V5V5V5V(*2)(*2)5V5V(*2)
7
Encoder
output
type
Output
circuit
Complimentary
Differential Differential Differential Differential (*2) (*2) Differential Differential (*2)
Terminating
resistance
No Yes Yes Yes Yes (*2) (*2) Yes Yes (*2)
8
Electronic
thermal
relay
Pr. 9 setting 0 0
Rated
motor
current
Rated
motor
current
Rated
motor
current
(*2) (*2)
Rated
motor
current
Rated
motor
current
(*2)
9
Thermal
protector
input
Across
OH-SD
Connect to
the thermal
Connect to
the thermal
Open Open Open (*2) (*2) Open Open (*2)
Pr. 876 setting
1 1000(*2)(*2)00(*2)
CAUTION
1. Set number of motor poles in Pr.81.
2. Make setting according to the motor used.
3. The half-tone screened cells are factory set.
4. Check the power supply specification of encoder and change a jumper connector.
5. *:Perform offline auto tuning (mode without rotation) for the wiring length to be reflected on the
control when exercising magnetic flux observer and the wiring length is long (30m or longer as
reference).
Offline auto tuning
The inverter measures necessary motor circuit constant and stores it to improve low speed
torque.
Online auto tuning
High torque accuracy corresponding to the motor temperature variation is available.