Instruction manual

25
Basic operation (Speed setting, run,
speed meter adjustment)
RUN AND OPERATION
3
z External jog operation
Keep the start switch (STF or STR) on to perform operation, and turn it off to stop.
1)Set Pr. 15 "jog speed setting" and Pr. 16 "jog acceleration/deceleration time".
2)Select the external operation mode.
3)Switch on the jog signal. Keep the start switch (STF or STR) on to perform operation.
Assign the terminal used for the jog signal in any of Pr. 180 to Pr. 183 and Pr. 187
(input terminal function selection). (Refer to page 65.)
(3) Choosing external/PU combined operation mode 1 (operation using the external start
signal and control panel)
z When setting the start signals from outside inverter (e.g. switches or relays) and the
running speed from the control panel (Pr. 79 = 3)
•Run command: start signal connected outside
•Speed setting: of PU or multi-speed command (multi-speed command has priority)
For multi-speed command, refer to Pr.4 to Pr.6 on page 54.
REMARKS
When setting the start signal from the PU and speed setting signal from outside inverter, set "4" (combined operation mode 2)
in Pr.79 "operation mode selection".
2.
4.
3.
5.
1.
FR-DU04
-1
CONTROL PANEL
Hz/r
MON EXT PU
A
V
REV FWD
FR-DU04
-1
CONTROL PANEL
Hz/r
MON EXT PU
A
V
REV FWD
Power on
Switch power on.
Operation mode selection
Set "3" in Pr. 79 "operation mode selection".
The combined operation mode is selected and the operation
status indication "EXT" and "PU" are lit.
Flicker
Start
Turn on the start switch (STF or STR).
The operation status indication "FWD" or "REV" is lit.
REMARKS
• The motor does not start if both the forward and
reverse rotation switches are turned on. If both
switches are turned on during operation, the motor
decelerates to a stop.
• Set the speed in the speed setting mode
Running speed setting
Using , of PU, set the running speed to 150r/min
The run command indication FWD or REV is lit.
Stop
Turn off the start switch (STF or STR).
The motor decelerates to stop.
Operation
Display
FR-DU04
-1
CONTROL PANEL
Hz/r
MON EXT PU
A
V
REV FWD
When Pr. 75 "PU stop selection" = "14 to 17",
CAUTION
and press .
SET
The operation status indication "FWD" or "REV" is lit.
SET
STOP
RESET
is valid.
Forward
rotation
Reverse
rotation
ON
Forward
rotation
Reverse
rotation
OFF
ON
(Refer to page 56 for details of Pr.79.)
(Refer to page 28.).