Instruction manual

Function list (Extended function parameters)
59
PARAMETERS
PARAMETERS
5
Operation selection functions
24
Multi-speed setting
(speed 4)
By setting a value other than "9999", set speeds 4 to 7.
ON/OFF of the contact signals (RH, RM, RL signals) are combined to change the
running speed in stages.
0 to 3600r/min, 9999
9999
{{
×*
25
Multi-speed setting
(speed 5)
9999
{{
×*
26
Multi-speed setting
(speed 6)
9999
{{
×*
27
Multi-speed setting
(speed 7)
9999
{{
×*
28
Multi-speed input
compensation
The multiple speeds can be increased or overridden for compensation.
0: Without compensation
1: With compensation
0
{{
×
29
Acceleration/
deceleration pattern
Determines the frequency changing pattern for acceleration/deceleration.
0: Linear acceleration/deceleration
1: S-pattern acceleration/deceleration A
2: S-pattern acceleration/deceleration B
3: Backlash measures acceleration/deceleration
4: S-pattern acceleration/deceleration C
0
{{
×
30
Regenerative
function selection
Set when using the FR-ABR, FR-HC or FR-CV option for frequent start/stop operation.
0: Internal brake resistor, brake unit
1: Brake resistor (FR-ABR)
2: High power factor converter (FR-HC), power regeneration common converter (FR-
CV)
0
{{{
31 Speed jump 1A
Set the speed ranges you want to avoid during constant-speed operation to avoid
resonance with the machine.
0 to 3600r/min, 9999
9999
{{
×
32 Speed jump 1B
9999
{{
×
33 Speed jump 2A
9999
{{
×
34 Speed jump 2B
9999
{{
×
35 Speed jump 3A
9999
{{
×
36 Speed jump 3B
9999
{{
×
Display
function
37 Speed display
Display the machine speed and output speed.
0: Output speed
1 to 9998: Machine speed at the Pr. 505 set speed operation
0
{{{
Output terminal
functions
41
Up-to-speed
sensitivity
You can adjust the output signal on/off range when the output speed reaches the
running speed.
0 to 100%
10%
{
××
42 Speed detection
You can adjust the speed detected.
0 to 3600r/min
300r/min
{{{
43
Speed detection for
reverse rotation
You can change the speed detection level for forward or reverse rotation in vertical lift,
transfer and other applications.
0 to 3600r/min, 9999
9999
{{{
Second functions
44
Second acceleration/
deceleration time
Second function of the acceleration/deceleration time set in Pr. 7, Pr. 8.
0 to 3600s/0 to 360s
5s
{{
×*
45
Second deceleration
time
Second function of the deceleration time set in Pr. 8.
0 to 3600s/0 to 360s, 9999
9999
{{
×*
Output terminal
functions
50
Second speed
detection
Set the speed at which the FB2 signal is output.
0 to 3600r/min
750r/min
{{{
Function
Parameter
Name Outline
Factory
Setting
Cus-
tomer
Set-
ting
At-a-glance Guide to
Functions
{: Usable function
×: Unusable function
* :
Functions that can be used
for parameter-set position
control
Vector Control
Speed
control
Torque
control
Position
control
RH RM RL
Speed 4 OFF ON ON
Speed 5 ON OFF ON
Speed 6 ON ON OFF
Speed 7 ON ON ON