Instruction manual

Function list (Extended function parameters)
60
Display functions
52
DU/PU main display
data selection
You can select the DU/PU main display data.
0, 100: Speed, output current, output voltage, alarm display
5: Preset speed
6: Output frequency
7: Motor torque
8: Converter output voltage
9: Regenerative brake duty
10: Electronic thermal relay function load factor
11: Output current peak value
12: Converter output voltage peak value
17: Load meter
18: Motor excitation current
19: Position pulse
20: Cumulative energization time
23: Actual operation time
24: Motor load factor
32: Torque command
33: Torque current command
34: Motor output
35: Feedback pulse
38: Trace status
0
{{{
53
PU level display data
selection
You can select the PU level display data.
0: No monitor
1: Speed
2: Output current
3: Output voltage
5: Preset speed
6: Output frequency
7: Motor torque
8: Converter output voltage
9: Regenerative brake duty
10: Electronic thermal relay function load factor
11: Output current peak value
12: Converter output voltage peak value
17: Load meter
18: Motor excitation current
1
{{{
Display functions
54
DA1 terminal function
selection
You can select the monitor output DA1 data.
1: Speed
2: Output current
3: Output voltage
5: Preset speed
6: Output frequency
7: Motor torque
8: Converter output voltage
9: Regenerative brake duty
10: Electronic thermal relay function load factor
11: Output current peak value
12: Converter output voltage peak value
17: Load meter
18: Motor excitation current
21: Reference output
32: Torque command
33: Torque current command
34: Motor output
36: Torque monitor (driving/regenerative polarity switching)
1
{{{
55
Speed monitoring
reference
You can set the reference value of speed monitoring.
0 to 3600r/min
1500r/min
{{{
56
Current monitoring
reference
You can set the reference value of current monitoring.
0 to 500A
Rated
inverter
current
{{{
Automatic restart
57 Restart coasting time
When power is restored after an instantaneous power failure, you can start the inverter
without stopping the motor (in a coasting status). When this time (Pr. 57) elapses after
power was restored, the inverter begins to restart.
When you set "9999", the inverter will not restart. Generally, setting of "0" does not
pose a problem, but the time can be adjusted (0, 0.1 to 5s, 9999) according to the
magnitude of the load.
When the restart coasting time (Pr. 57) elapses, the output voltage is risen gradually.
Set this cushion time (Pr. 58) (0 to 60s).
Normally, you can perform operation with the factory settings, but you can adjust them
according to the load magnitude. (Pr. 58 is valid only during V/F control)
9999
{{
×
58 Restart cushion time
1.0s
×××
Additional function
59
Remote setting
function selection
You can make remote setting of the speed when the control panel is located away from
the control box.
0: None
1: With remote setting function, with frequency setting storage function
2: With remote setting function, without frequency setting storage function
3: With remote setting function, without frequency setting storage function
(Turning STF/STR off clears remote setting)
0
{{
×
Operation selection functions
60
Intelligent mode
selection
Set when using the brake sequence control.
0: Normal operation mode
7: Brake sequence mode
(With mechanical brake opening completion signal input)
8: Brake sequence mode
(Without mechanical brake opening completion signal input)
0
{
××
Function
Parameter
Name Outline
Factory
Setting
Cus-
tomer
Set-
ting
At-a-glance Guide to
Functions
{: Usable function
×: Unusable function
* :
Functions that can be used
for parameter-set position
control
Vector Control
Speed
control
Torque
control
Position
control