Instruction manual

77
Errors (Alarms)
ERRORS AND PROTECTIVE FUNCTIONS
6
*5:The FR-A5NR (relay output/computer(Check the stall prevention operation level (Pr. 22) setting if V/F control is
exercised.)
link) allows one more communication option to be fitted. In this case, only relay output is usable and
computer link is unusable.
Control Panel
Indication
E.GF FR-PU04V Ground Fault
Name
Output side earth (ground) fault overcurrent
Description
This function stops the inverter output if an earth (ground) fault overcurrent flows due to an earth
(ground) fault that occurred in the inverter's output (load) side.
Check point
Check for an earth (ground) fault in the motor and connection cable.
Corrective action
Remedy the earth (ground) fault portion.
Control Panel
Indication
E.OHT FR-PU04V OH Fault
Name
External thermal relay operation
Description
If the external thermal relay provided for motor overheat protection, or the internally mounted
temperature relay in the motor, etc. switches on (contacts open), the inverter output is stopped.
Even if the relay contacts are reset automatically, the inverter will not restart unless it is reset.
Check point
Check for motor overheating.
Corrective action
Reduce the load and operating duty.
Control Panel
Indication
E.OLT FR-PU04V
Stll Prev STP (OL shown during stall
prevention operation)
Name
Motor overload
Description
For V/F control, the stall prevention function is activated if the current flow in the motor exceeds
150% (factory setting) of the inverter rated current, an alarm stop is made if the status that the
output frequency is lowered at 0Hz persists for 3s.
For speed/position control, if the torque limit is activated under high load, the motor stalls to the
speed less than the low speed detection (Pr. 865) value, and an alarm stop is made if the status
that the output torque is more than the OLT level setting (Pr. 874) value persists for 3s.
This function is not activated for torque control.
Check point
Check the motor for use under overload.
Check that the low speed detection (Pr. 865) and OLT level setting (Pr. 874) values are correct.
(Check the stall prevention operation level (Pr. 22) setting if V/F control is exercised.)
Corrective action
Reduce the load weight.
Change the stall prevention operation level (Pr. 22), low speed detection (Pr. 865) and OLT level setting
(Pr. 874) values. (Check the stall prevention operation level (Pr. 22) setting if V/F control is exercised.)
Control Panel
Indication
E.OPT FR-PU04V Option Fault
Name
Option alarm
Description
Stops the inverter output when two or more communication options are mounted. (*5)
When the high power factor converter (FR-HC) or power regeneration common converter (FR-CV)
is connected, this alarm appears if an AC power supply is connected to the R, S, T terminals
accidentally.
Check point
Check that the number of communication options mounted is one.
When the high power factor converter (FR-HC) or power regeneration common converter (FR-
CV) is connected, check that an AC power supply is not connected to the R, S, T terminals.
When the parameter set is for the option use, the option is not fitted nor connected securely.
Corrective action
Mount only one communication option.
Check the Pr. 30 setting and wiring.
Check the Pr. 419 and Pr. 804 settings.
When the high power factor converter (FR-HC) or power regeneration common converter (FR-
CV) is connected, connecting an AC power supply to the R, S, T terminals may damage the
inverter. Please contact your sales representative.