10 TROUBLESHOOTING
10-1. TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the control board of outdoor unit. Actions to be taken for service,
which depends on whether or not the trouble is reoccurring at service, are summarized in the table below. Check the contents
below before investigating details.
Unit conditions at service Error code Actions to be taken for service (summary)
The trouble is reoccurring.
Displayed
Judge what is wrong and take a corrective action according to
“10-3. Self-diagnosis action table”.
Not displayed
Conduct troubleshooting and ascertain the cause of the
trouble.
The trouble is not reoccurring.
Logged
1
Consider the temporary defects such as the work of
protection devices in the refrigerant circuit including
compressor, poor connection of wiring, noise and etc. Re-
check the symptom, and check the installation environment,
refrigerant amount, weather when the trouble occurred,
matters related to wiring and etc.
2
Reset error code logs and restart the unit after nishing
service.
3
There is no abnormality in electrical component, controller
board, and etc.
Not logged
1
Re-check the abnormal symptom.
2
Conduct troubleshooting and ascertain the cause of the
trouble.
3
Continue to operate unit for the time being if the cause is
not ascertained.
4
There is no abnormality concerning of parts such as
electrical component, controller board, and etc.
10-2. CHECK POINT UNDER TEST RUN
Before test run
After installation of outdoor unit, piping work and electric wiring work, re-check that there is no water leakage, loosened con-
nections and incorrect polarity.
Measure impedance between the ground and the power supply terminal block (L, N) on the outdoor unit by 500 V Megger
and check that it is 1.0 M or over.
Turn on power supply 12 hours before test run in order to protect compressor.
Make sure to read operation manual before test run. (Especially items to secure safety.)
Warning:
Do not use the system if the insulation resistance is less than 1.0 MΩ.
Caution:
Do not carry out this test on the control wiring (low voltage circuit) terminals.