Phenomena
Factor
Countermeasure
7. Remote controller display works
normally and the unit performs
heating operation, however, the
capacity cannot be fully obtained.
1Linear expansion valve fault
Opening cannot be adjusted well due to linear expan-
sion valve fault.
2Refrigerant shortage
3Lack of insulation for refrigerant piping
4Filter clogging
5Heat exchanger clogging
6Air duct short cycle
7Bypass circuit of outdoor unit fault
1Discharging temperature and indoor heat
exchanger temperature does not rise.
Inspect the failure by checking discharg-
ing pressure.
Replace linear expansion valve.
2If refrigerant leaks, discharging tempera
ture rises and LEV opening increases.
Inspect leakage by checking the tem-
perature and opening.
Check pipe connections for gas leakage.
3Check the insulation.
4Open intake grille and check the filter.
Clean the filter by removing dirt or dust on
it.
5If the filter is clogged, indoor pipe tem-
perature rises and discharging pressure
increases. Check if heat exchanger is
clogged by inspecting discharging pres-
sure.
Clean the heat exchanger.
6Remove the blockage.
7Check refrigerant system during operation.
8. 1For 3 minutes after temperature
adjuster turns off, the compressor
will not start operating even if tem-
perature adjuster is turned on.
2For 3 minutes after temperature
adjuster turns on, the compressor
will not stop operating even if tem-
perature adjuster is turned off.
(Compressor stops operating
immediately when turning off by
the remote controller.)
12Normal operation
(For protection of compressor)
12Normal operation