Service manual

35
Notes
· High voltage is applied to the connecter (CNF1, 2) for the fan motor. Pay attention to the service.
· Do not pull out the connector (CNF1, 2) for the motor with the power supply on.
(It causes trouble of the outdoor controller circuit
board and fan motor.)
Self check
Symptom : The outdoor fan cannot turn around.
Check method of DC fan motor (fan motor / outdoor controller circuit board)
NG
NG
Wiring contact check
Contact of fan motor connector (CNF1, 2)
Fuse check
Check the fuse (F5) on outdoor
controller board.
Power supply check (Remove the connector (CNF1, 2))
Measure the voltage in the outdoor controller circuit
board.
TEST POINT
:VDC (between 1 (+) and 4 (-) of the fan connector): VDC DC250~330V
TEST POINT :VCC (between 5 (+) and 4 (-) of the fan connector): VCC DC15V
Recover wiring.
Replace outdoor controller board.
Replace the fan motor.
Replace outdoor controller board (C.B)
and fan motor (MF1, 2).
Replace outdoor
controller board.
Replace the fan motor.
Is the voltage normal?
Is there contact failure?
Yes
No
Did the fuse blow?
No
Yes
Check the operation of fan. END
Yes
OK
Check the operation. END
OK
Yes
No
10-7. HOW TO CHECK THE COMPONENTS
0.5
2.5 5
2.5
4.5
Vout (V)
PRESSURE
(MPa)
3
2
1
WHT
BLU
BLK
SENSOR
5V DC
GND
63HS
Vout
MICRO
PROCESSOR
MULTI
CONTROLLER BOARD
- : 5V (DC)
- : Output Vout (DC)
<HIGH PRESSURE SENSOR>
OCH525