Installation manual

- 9 -
* Main and sub system controllers (M-NET)
AG-150A is for exclusive use as a main SC. AG-150A cannot be used as a sub SC.
Main system controller (Main SC)
Main SC refers to a controller that controls all other system controllers including the units they control. If a given system has
only one system controller, that controller becomes the main controller. Group settings and interlock settings can only be made
from a main controller.
Sub system controller (Sub SC)
Sub controller refers to a system controller that is controlled (including the units it controls) by a main system controller.
NOTES
* Up to three PAC-YG50ECA controllers can be connected to each AG-150A unit.
* Main system controllers (e.g., AG-150A) cannot be connected to an M-NET system that is controlled by an Expansion controller.
NOTES The following types of configurations are not possible.
A sub controller can only control the groups that are under the control of its main controller.
No groups can be placed under the control of more than one main system controller.
No sub system controllers can be placed under the control of more than one main system controller.
AG-150A, PAC-YG50ECA etc.
Range of units the main SC
controls (M-NET)
Group Group
Group
AG-150A is for exclusive use as a main SC. AG-150A cannot be used as a sub
SC or controlled from another main SC.
Range of units the
sub SC controls
Group Group Group
Main system
controller
Sub system
controller
Group Group Group
Main system
controller 1
Main system
controller 2
Group Group Group Group
Main system
controller 1
Sub system
controller
Main system
controller 2
WT05368X08.fm Page 9 Thursday, March 17, 2011 9:21 AM