Installation manual

- 23 -
System 1: Standard configuration (system with 50 units of equipments or less)
System 2: System with connection to one or more Expansion controllers (system with more than 50 units or equipments)
The startup procedures vary with system configuration.
The following table summarizes the initial setting procedures.
8 Initial Setting
NOTES
* Choose from two initial setting methods: 1) Making the settings via AG-150A, 2) Making the setting via the LAN using the Initial
Setting Web.
This manual provides the instructions on making the initial settings from AG-150A.
Please refer to AG-150A Instruction Book or the Instruction Book that are provided with Initial Setting Web.
Refer to the PAC-YG50ECA Expansion controller Installation/Instructions Manual for how to connect Expansion controllers.
Initial setting procedures
System configuration
12
1. Startup 1 Check that the version of the AG-150A software is 2.10 or later.
Check that the DB No. of the AG-150A and the PAC-YG50ECA to be
connected match.
2 Set the IP address for the Expansion controller with the dipswitch on
PAC-YG50ECA.
13
Turn on the power supply unit (PAC-SC51KUA) to start up the AG-150A.
(Turn on the Expansion controllers as well for System 2.)
24The display language selection window will appear. Select the desired
language by touching the language.
35The Initial Setting screen will appear.
(Once the initial settings have been made, the monitor screen will
appear when the unit is turned on. Touch the icon at the top right of
the screen to bring up the Initial Settings window if necessary.)
2. Clock setting 1 Touch “Date and time” on the Initial Settings window.
2 Change other settings as necessary by touching the desired items, and
touch “Save Settings” to save the changes.
3. Unit information settings 11Touch “Unit Info.” on the Initial Settings window.
2 Set the Expansion Controller setting to “Do not use”.
2 Set the Expansion Controller setting to “Use”.
33Change other settings as necessary by touching the desired items, and
touch “Save Settings” to save the changes.
4. Network settings 11Touch “Network” on the Initial Settings window.
2 Check that the AG-150A tab is selected.
3 Touch the EC tabs, and make necessary settings for the EC-1 through
EC-3.
24Change other settings as necessary by touching the desired items, and
touch “Save Settings” to save the changes.
5. Group settings 11Touch “Groups” on the Initial Settings window.
2 Touch the EC tabs, and make necessary settings for the EC-1 through
EC-3.
23Change other settings as necessary by touching the desired items, and
touch “Save Settings” to save the changes.
6. Miscellaneous settings 11After completing the group setting, make the settings for other items as
necessary by touching the item on the menu to be set.
Interlocked operation setting (interlocked operation between
LOSSNAY and indoor units)
Refrigerant system monitor (monitoring of refrigerant piping
connection between indoor and outdoor units)
Block settings
Floor layout settings
User settings
7. Clock setting 11Touch “Date and time” on the Initial Settings window.
22Change other settings as necessary by touching the desired items, and
touch “Save Settings” to save the changes.
8. Exiting the Initial Settings
window
11When all settings have been completed, touch the icon to return to
the Monitor/Operation window.
WT05368X08.fm Page 23 Thursday, March 17, 2011 9:21 AM