Installation manual

- 25 -
1. System with connection to a PAC-YG50ECA Expansion controller
2. Using multiple system controllers
Make the initial settings (e.g., group settings and interlock settings) from the AG-150A, which is a main system controller, or
from the Initial Settings Web.
Designate a single system controller in a given system from which operation prohibition signal can be sent.
3. To control a Mr. Slim
* An M-NET adapter (sold separately) is required to
connect and control the Mr. Slim model of units to the
M-NET.
4. To control a K control model
* Set AG-150A address to “000” when a K transmission converter is
connected. Always set to the main system controller when the
address is “000”.
* Set the address of the K-control indoor units to a larger number
than those of the M-transmission models of indoor units.
* When using a group setting for the K control model, set only the
indoor unit that belongs to that group.
* Set the minimum indoor unit address in the group for the K control
model group number.
10 System Configuration Example
AG-150A
192.168.1.1
24VDC
Switching
HUB
LAN LAN
Expansion controller
(PAC-YG50ECA)
192.168.1.211
000
Expansion controller
(PAC-YG50ECA)
192.168.1.212
000
Expansion controller
(PAC-YG50ECA)
192.168.1.213
000
M-NET
M-NET
M-NET
ON/OFF remote
controller etc.
201
M-NET adapter
K transmission converter (Model name: PAC-SC25KAA)
Indoor units: 50 units
Indoor unit: 20 units
Indoor unit address 01 ~ 20
Group 1 ~ Group 20
Mr. Slim outdoor unit (M-NET
adapter)
M-NET adapter: 2 units
M-NET adapter address 21 ~ 22
Group 21, 22
Indoor unit (M-NET): 20 units
Indoor unit address 01 ~ 20
Group 1 ~ Group 20
Indoor unit (K-control): 30 units
Indoor unit address 21 ~50
Group 21 ~ Group 50
: IP address
: M-NET address
Power supply unit for transmission line
(Model name: PAC-SC51KUA)
*1 M-NET address settings
are not required.
*1
AG-150A
000
ON/OFF remote
controller etc.
201
(Main system controller)
(Sub system controller)
24VDC
Indoor units: 50 units
Group 1 ~ Group 20
Power supply unit for transmission line (Model name: PAC-SC51KUA)
AG-150A
000
M-NET adapter
Indoor unit address 01 ~ 20
Group 1 ~ Group 20
Mr. Slim outdoor unit (M-NET
adapter)
M-NET adapter: 2 units
M-NET adapter address 21 ~ 22
Group 21, 22
Power supply unit for transmission line (Model name: PAC-SC51KUA)
(Main system controller)
20 indoor units
Indoor unit address 01~20
Group 1 to Group 20
20 indoor units (for control)
Indoor unit address 21~40
Group 21 to Group 40
M-NET
PAC-SC51KUA
Power supply unit
24VDC
(Main system controller)
AG-150A
PAC-SC25KAA
K transmission converter