Installation manual

- 27 -
(4) Recommended circuit
(A) For level signal
(B) For pulse signal
1 The contact relay, DC power source, extension cable, etc., must be prepared on site.
2 The connection cable can be extended up to 10m (32 ft). Use a 0.3mm
2
(AWG 22) or larger wire.
3 Strip the extra cable near the connector, and insulate the exposed section securely with tape, etc.
2. External signal output function
* External signal output requires the external I/O adapter PAC-YG10HA (sold separately).
(1) External output
When one or more air conditioners are operating, the “ON” signal will be output, if a malfunction occurs in one or more air
conditioners, the “Malfunction” signal will be output.
(2) External output specifications
(3) Recommended circuit
1 Each element will turn on while in ON operation or if a malfunction occurs.
2 The connection cable can be extended up to 10m (32 ft).
3 The relays, lamps, diodes and extension cables, etc, must be prepared separately on site.
NOTE
* When using a PAC-YG50ECA Expansion controller, connect the external input/output adapter to the external input terminal on
the Expansion controller, not to the AG-150A.
CN5 Lead wire Details of each terminal
No.1 Green Common (External ground)
* The operation status of DIDO controller is not output.
* Operation signal is output during an error.
No.2 Black ON/OFF*
No.3 Brown Malfunction/normal
CN5
Red
Orange
Max.10m
(32 ft)
X1
X1
Run/stop or
Emergency stop
Power supply
(12VDC or 24VDC)
This unit
9
8
7
6
5
1
Use relays X1, X2, Y1, and Y2 that meet the
following specifications.
Contact rating
Rated voltage >=12VDC
Rated current >= 0.1A
Minimum applicable load =< 1mA at DC
Important
Be sure to use 12VDC or 24VDC for a
power supply.
Connect the power supply with correct
polarity.
Improper connection may result in malfunctions.
CN5
9
8
7
6
5
1
Power supply
(12VDC or 24VDC)
Red
Gray
Blue
Yellow
Orange
Max.10m
(32 ft)
This unit
Run Stop
Prohibit
Enable
X1 X2 Y1 Y2
Y2
Y1
X2
X1
Use Z1 and Z2 relays that meet the following specifications.
Operation coil
Rated voltage: 12VDC, 24VDC
Power Consumption: 0.9W or less
(*1) Prepare a power supply separately according to the
relay being used (12VDC or 24VDC).
(*2) Always include a diode on both ends of the relay coil.
Important
Be sure to use 12VDC or 24VDC for a power supply.
Connect the power supply with correct polarity.
Do not connect the power supply without relays
being connected to the controller. (no load)
Improper connection may result in malfunctions.
CN5
9
4
3
2
1
Brown
Black
Green
Max.10m
(32 ft)
L1Z1
L2
Z2
Z2
Z1
Power (*1)
Supply
Diode (*2)
(*2)
(*2)
This unit L1: Run display lamp
L2: Malfunction display lamp
WT05368X08.fm Page 27 Thursday, March 17, 2011 9:21 AM