Engineering Manual

A-137
2) HEATING CAPACITY
Model
Indoor air Outdoor intake air WB temperature (˚F)
IDB (˚F)
5 15 25 35 43 45 55
TC TPC TC TPC TC TPC TC TPC TC TPC TC TPC TC TPC
MUZ-FH06NA
75 3.8 0.32 5.0 0.41 6.3 0.48 7.5 0.53 8.5 0.56 8.7 0.57 9.9 0.59
70 4.1 0.31 5.4 0.39 6.5 0.47 7.7 0.52 8.7 0.55 9.0 0.56 10.1 0.58
65 4.4 0.29 5.5 0.38 6.8 0.45 8.0 0.50 9.0 0.53 9.2 0.54 10.4 0.57
MUZ-FH06NAH
75 3.8 0.45 5.0 0.53 6.3 0.60 7.5 0.53 8.5 0.55 8.7 0.56 9.9 0.58
70 4.1 0.44 5.4 0.52 6.5 0.59 7.7 0.51 8.7 0.54 9.0 0.55 10.1 0.57
65 4.4 0.42 5.5 0.50 6.8 0.58 8.0 0.50 9.0 0.53 9.2 0.53 10.4 0.56
MUZ-FH09NA
75 4.8 0.42 6.3 0.53 7.9 0.62 9.4 0.69 10.6 0.73 11.0 0.74 12.4 0.77
70 5.2 0.40 6.7 0.51 8.2 0.61 9.6 0.67 10.9 0.71 11.2 0.72 12.7 0.75
65 5.5 0.38 6.9 0.49 8.6 0.59 10.0 0.66 11.2 0.69 11.6 0.70 13.0 0.74
MUZ-FH09NAH
75 4.8 0.55 6.3 0.66 7.9 0.75 9.4 0.69 10.6 0.73 11.0 0.74 12.4 0.77
70 5.2 0.53 6.7 0.64 8.2 0.74 9.6 0.67 10.9 0.71 11.2 0.72 12.7 0.75
65 5.5 0.51 6.9 0.62 8.6 0.72 10.0 0.66 11.2 0.69 11.6 0.70 13.0 0.74
MUZ-FH12NA
75 6.0 0.56 7.9 0.71 9.9 0.83 11.8 0.93 13.3 0.97 13.7 0.99 15.5 1.03
70 6.5 0.54 8.4 0.68 10.2 0.81 12.0 0.90 13.6 0.95 14.0 0.97 15.8 1.01
65 6.8 0.51 8.6 0.66 10.7 0.78 12.4 0.88 14.0 0.93 14.4 0.94 16.2 0.99
MUZ-FH12NAH
75 6.0 0.69 7.9 0.84 9.9 0.96 11.8 0.93 13.3 0.97 13.7 0.99 15.5 1.03
70 6.5 0.67 8.4 0.81 10.2 0.94 12.0 0.90 13.6 0.95 14.0 0.97 15.8 1.01
65 6.8 0.64 8.6 0.79 10.7 0.91 12.4 0.88 14.0 0.93 14.4 0.94 16.2 0.99
MUZ-FH15NA
75 7.9 0.77 10.4 0.97 13.1 1.14 15.6 1.27 17.6 1.33 18.1 1.35 20.5 1.40
70 8.6 0.73 11.1 0.94 13.5 1.11 15.9 1.24 18.0 1.30 18.5 1.33 21.0 1.38
65 9.0 0.70 11.3 0.90 14.1 1.07 16.5 1.20 18.5 1.27 19.1 1.29 21.4 1.35
MUZ-FH15NAH
75 7.9 0.90 10.4 1.10 13.1 1.27 15.6 1.27 17.6 1.33 18.1 1.35 20.5 1.40
70 8.6 0.86 11.1 1.07 13.5 1.24 15.9 1.24 18.0 1.30 18.5 1.33 21.0 1.38
65 9.0 0.83 11.3 1.03 14.1 1.20 16.5 1.20 18.5 1.27 19.1 1.29 21.4 1.35
MUZ-FH18NA2
75 8.9 1.01 11.8 1.28 14.7 1.51 17.6 1.68 19.8 1.76 20.4 1.79 23.1 1.86
70 9.6 0.97 12.5 1.24 15.2 1.47 18.0 1.63 20.3 1.72 20.9 1.75 23.6 1.82
65 10.2 0.93 12.8 1.19 15.9 1.42 18.6 1.59 20.9 1.68 21.5 1.70 24.2 1.79
MUZ-FH18NAH2
75 8.9 1.14 11.8 1.41 14.7 1.64 17.6 1.68 19.8 1.76 20.4 1.79 23.1 1.86
70 9.6 1.10 12.5 1.37 15.2 1.60 18.0 1.63 20.3 1.72 20.9 1.75 23.6 1.82
65 10.2 1.06 12.8 1.32 15.9 1.55 18.6 1.59 20.9 1.68 21.5 1.70 24.2 1.79
NOTE: 1. IDB : Intake air dry-bulb temperature
TC : Total Capacity (x10
3
Btu/h) TPC : Total Power Consumption (kW)
2. Above data is for heating operation without any frost.
How to operate with fixed operational frequency of the compressor.
1. Press the EMERGENCY OPERATION switch on the front of the indoor unit, and select either EMERGENCY COOL
mode or EMERGENCY HEAT mode before starting to operate the air conditioner.
2. The compressor starts with operational frequency.
3. The fan speed of the indoor unit is High.
4. This operation continues for 30 minutes.
5. In order to release this operation, press the EMERGENCY OPERATION switch twice or once, or press any button on
the remote controller.