Engineering Manual

A-232
MUZ-HM12NA
-
U1
HEATING CAPACITY
Outdoor Temperature Degrees (°F)
-4.0 5.0 14.0 23.0 32.0 41.0 50.0 69.8 75.0
% Heating Capacity 48% 61% 74% 83% 92% 100% 100% 100% 100%
0%
20%
40%
60%
80%
100%
120%
-4 5 15 25 35 45 55 65 75
% Heating Capacity
Outdoor Temperature Degrees (°F)
MUZ-HM12NA
-
U8
HEATING CAPACITY
Outdoor Temperature Degrees (°F)
-4.0 5.0 14.0 23.0 32.0 41.0 50.0 69.8 75.0
%001%001%001%79%49%19%68%67%76% Heating Capacity
0%
20%
40%
60%
80%
100%
120%
5 15 25 35 45 55 65 75
% Heating Capacity
Outdoor Temperature Degrees (°F)
-4