Engineering Manual

A-24
MUZ-FE09NAH MUZ-FE12NAH
Outdoor unit model MUZ-FE09NAH MUZ-FE12NAH
Capacity
Rated (Minimum~Maximum)
Cooling 1
Btu/h 9,000 (2,800~9,000) 12,000 (2,800~12,000)
Heating 47 1
Btu/h 10,900 (3,000~18,000) 13,600 (3,000~21,000)
Capacity
Rated (Maximum)
Heating 17 2
Btu/h 6,700 (12,500) 7,900(13,600)
Power consumption
Rated (Minimum~Maximum)
Cooling 1
W 580 (160~650) 930 (160~960)
Heating 47 1
W 710 (150~2,250) 950 (150~2,250)
Power consumption
Rated (Maximum)
Heating 17 2
W 650 (1,730) 750(1,780)
EER
1
[SEER]
3
Cooling 15.5 [26.0] 12.9 [23.0]
HSPF IV
4
Heating 10.0 10.1
COP Heating
1 4.50 4.20
Power factor
Cooling (208/230) % 99/98 99/98
Heating (208/230) % 98/99 99/99
Power supply V , phase , Hz 208/230, 1 , 60
Max. fuse size (time delay) A 15
Min. circuit ampacity A 12
Fan motor F.L.A 0.56
Compressor
Model SNB130FQBHT
R.L.A 8.6
L.R.A 10.8
Refrigeration oil
 oz. (L) (Model)
15.2 (0.45)/(NEO22)
Refrigerant control Linear expansion valve
Sound level
1
Cooling dB(A) 48 48
Heating dB(A) 49 49
Defrost method Reverse cycle
Dimensions
W in. 31-1/2
D in. 11-1/4
H in. 21-5/8
Weight lb. 80
External nish Munsell 3Y 7.8/1.1
Remote controller Wireless type
Control voltage
(by built-in transformer)
VDC 12 - 24
Refrigerant piping Not supplied
Refrigerant pipe size
(Min. wall thickness)
Liquid in. 1/4 (0.0315)
Gas in. 3/8 (0.0315)
Connection method
Indoor Flared
Outdoor Flared
Between the indoor
& outdoor units
Height difference ft. 40
Piping length ft. 65
Refrigerant charge (R410A) 2 lb. 9 oz.
NOTE: Test conditions are based on AHRI 210/240.
1: Rating conditions (Cooling) Indoor: 80˚FDB, 67˚FWB, Outdoor: 95˚FDB, (75˚FWB)
(Heating) Indoor: 70˚FDB, 60˚FWB, Outdoor: 47˚FDB, 43˚FWB
2: (Heating) Indoor: 70˚FDB, 60˚FWB, Outdoor: 17˚FDB, 15˚FWB