Engineering Manual

A-32
OUTLET AIR SPEED AND COVERAGE
SLZ-KA09NA SLZ-KA12NA SLZ-KA15NA
Indoor unit model SLZ-KA09NA SLZ-KA12NA SLZ-KA15NA
Power supply V, phase, Hz 208/230, 1, 60
Max. fuse size (time delay)/Disconnect switch
A 15
Min. circuit ampacity A 1.0
Fan motor F.L.A 0.23 0.28 0.28
Airow
(Low - Med. - High)
Dry CFM 280-320-350 280-320-390 280-320-390
Wet CFM 250-290-320 250-290-350 250-290-350
Moisture removal pt/h 1.2 2.3 4.5
Sound pressure level (Low - Med. - High) dB(A) 29-32-38 30-34-39 31-35-40
External nish color Unit: Galvanized sheets with gray heat insulation
Grille: ABS resin Munsell 6.4Y 8.9/0.4
Dimensions unit <Grille> W in. 22-7/16 <25-19/32>
D in. 22-7/16 <25-19/32>
H in. 8-3/16 <25/32>
Weight unit <Grille> lb. 36 <7>
Field drainpipe O.D. in. 1-1/4
Control voltage (by buit-in transformer) 12 - 24 VDC
NOTE : Test conditions are based on AHRI 210/240.
Model Function
Airow
(CFM)
Air speed
(ft./s.)
Coverage
(ft.)
SLZ-KA09NA
Dry 350 11.2 12.1
Wet 320 10.2 11.1
SLZ-KA12NA
Dry 390 12.1 13.5
Wet 350 10.9 12.1
SLZ-KA15NA
Dry 390 12.1 13.5
Wet 350 10.9 12.1
The air coverage is the gure up to the position where the air speed is 1
ft./s., when air is blown out horizontally from the unit properly at the High
speed position.
The coverage should be used only as a general guideline since it varies
according to the size of the room and furniture arranged inside the room.