Engineering Manual

A-40
The air coverage is the figure up to the
position where the air speed is 1 ft./s.,
when air is blown out horizontally from
the unit properly at the High speed posi-
tion.
The coverage should be used only as a
general guideline since it varies accord-
ing to the size of the room and furniture
arranged inside the room.
OUTLET AIR SPEED AND COVERAGE
1. Single connection
Model Mode Function
Airow
(CFM)
Air speed
(ft./s.)
Coverage
(ft.)
MFZ-KJ09NA
MFZ-KJ12NA
HEAT Dry 417 20.3 29.6
COOL
Dry 417 20.3 29.6
Wet 354 17.2 25.3
MFZ-KJ15NA
HEAT Dry 470 22.9 33.3
COOL
Dry 431 21.0 30.6
Wet 366 17.8 26.2
MFZ-KJ18NA
HEAT Dry 470 22.9 33.3
COOL
Dry 491 23.9 34.8
Wet 417 20.3 29.7
2. Multi connection
Model Mode Function
Airow
(CFM)
Air speed
(ft./s.)
Coverage
(ft.)
MFZ-KJ09NA
MFZ-KJ12NA
HEAT Dry 343 16.7 24.5
COOL
Dry 275 13.4 19.8
Wet 234 11.4 16.9
MFZ-KJ15NA
MFZ-KJ18NA
HEAT Dry 470 22.9 33.3
COOL
Dry 374 18.2 26.7
Wet 318 15.5 22.8
(2) OPERATION
Mode Condition
Intake air temperature (°F)
Indoor Outdoor
DB WB DB WB
Cooling
Standard temperature 80 67 95
Maximum temperature 90 73 115
Minimum temperature 67 57 14
Maximum humidity 78%
Heating
Standard temperature 70 60 47 43
Maximum temperature 80 67 75 65
Minimum temperature 70 60 -13 -14
OPERATING RANGE
(1) POWER SUPPLY
Rated voltage Guaranteed voltage (V)
Indoor unit
208/230 V
1 phase
60 Hz
Min. 187
208 230 Max. 253