Engineering Manual

B-171
● The air coverage is the figure up to the
position where the air speed is 1 ft./s.,
when air is blown out horizontally from
the unit properly at the High speed posi-
tion.
The coverage should be used only as a
general guideline since it varies accord-
ing to the size of the room and furniture
arranged inside the room.
OUTLET AIR SPEED AND COVERAGE
1. Multi connection
Model Mode Function
Airow
(CFM)
Air speed
(ft./s.)
Coverage
(ft.)
MLZ-KP09NA
HEAT Dry 311 13.0 20.7
COOL
Dry 325 13.6 21.7
Wet
MLZ-KP12NA
HEAT Dry 332 13.9 22.1
COOL
Dry 350 14.6 23.3
Wet
MLZ-KP18NA
HEAT Dry 403 16.9 26.7
COOL
Dry 417 17.5 27.6
Wet
(2) OPERATION
*The operating range of the outdoor unit depends on the connected outdoor unit.
Mode Condition
Intake air temperature (°F)
Indoor Outdoor
DB WB DB WB
Cooling
Standard temperature 80 67 95
Maximum temperature 90 73 115
Minimum temperature 67 57 14
Maximum humidity 78%
Heating
Standard temperature 70 60 47 43
Maximum temperature 80 67 75 65
Minimum temperature 70 60 -13 -14
OPERATING RANGE
(1) POWER SUPPLY
Rated voltage Guaranteed voltage (V)
Indoor unit
208/230 V
1 phase
60 Hz
Min. 187
208 230 Max. 253