Spec Sheet

DIMENSIONS: PUZ-AN.A
)RUP6%B3VA$$$B38=$1.$B806
6SHFLILFDWLRQVDUHVXEMHFWWRFKDQJHZLWKRXWQRWLFH
ZZZ0LWVXELVKL(OHFWULFFD
0LWVXELVKL(OHFWULF6DOHV&DQDGD,QF 3DJH5 of 5
Rear Air Intake
Handle for
moving
Side Air Intake
1
2
Handle for moving
Handle for
moving
Service panel
Earth terminal
(
(
Terminal connection
Right
...
Indoor/Outdoor wiring
*1 442<17-2/5>
1063<41-7/8>
632<24-7/8>
*1 450<17-23/32>
26<1-1/32>
369 <14-17/32>
1338<52-11/16>
362<14-1/4>
1050 <41-11/32>
Air intake
Front piping cover
Rear piping cover
2-12×36 Oval holes
(Foundation Bolt M10<W3/8>)
Installation Feet
2-U Shaped notched holes
(Foundation Bolt M10<W3/8>)
225<8-27/32>
42<1-21/32>
60<2-3/8>
25<31/32>
330<13>
225<8-27/32>
600<23-5/8>
70<2-3/4>
417<16-13/32>
28<1-3/32>
370<14-9/16>
19<3/4>
40
<1-9/16>
53<2-3/32>
56<2-7/32>
0
Left
...
Power supply wirin
J
Example of Notes
1
...
Refrigerant GAS pipe connection (FLARE)
ø15.88(5/8F)
2
...
Refrigerant LIQUID pipe connection (FLARE)
ø9.52(3/8F)
*
1
...
Indication of STOP VALVE connection location.
Air Discharge
Rear Air Intake
Side Air Intake
8QLWPPLQ
Indoor terminal block
Ground wire
Outdoor terminal block
Outdoor terminal block
Power supply
Indoor-Outdoor S1-S2 ...... 208/230Vac
Indoor-Outdoor S2-S3 ................. 24Vdc
Indoor remote controlle .r ................. 12Vdc
power & control
indoor/outdoor
connecting cable
Should this document be altered or changed without MESCA’s permission, it becomes null and void. MESCA assumes no responsibility for any consequences in such cases. *