Gas Heater User Manual

Power
Code Electric Power
01 115/60/1
02 230/60/1
04 200/60/3
05 230/460/60/3
07 575/60/3
09 115/60/1
10 230/60/1
12 200/60/3
13 230/460/60/3
15 575/60/3
17 115/60/1
18 230/60/1
20 200/60/3
21 230/460/60/3
23 575/60/3
25 115/60/1
26 230/60/1
28 200/60/3
29 230/460/60/3
31 575/60/3
33 115/60/1
34 230/60/1
36 200/60/3
37 230/460/60/3
39 575/60/3
41 115/60/1
42 230/60/1
44 200/60/3
45 230/460/60/3
47 575/60/3
49 115/60/1
50 230/60/1
52 200/60/3
53 230/460/60/3
55 575/60/3
HP Drive HP Drive HP Drive HP Drive HP Drive HP Drive HP Drive HP Drive HP Drive HP Drive HP Drive
1/4 182 1/4 184 1/4 200 1/4 188 1/4 191 1/4 212
1/4 182 1/4 184 1/4 200 1/4 188 1/4 191 1/4 212
1/4 182 1/4 184 1/4 200 1/4 188 1/4 191 1/4 212
1/4 182 1/4 184 1/4 200 1/4 188 1/4 191 1/4 212
1/4 194 1/4 196 1/4 208 1/4 189 1/4 197 1/4 213
1/4 183 1/4 185 1/4 90 1/3 188 1/3 191 1/3 95 1/3 212 1/3 203 3/4 205 1 107 1-1/2 105
1/4 183 1/4 185 1/4 90 1/3 188 1/3 191 1/3 95 1/3 212 1/3 203 3/4 205 1 107 1-1/2 105
1/4 183 1/4 185 1/4 90 1/3 188 1/3 191 1/3 95 1/3 212 1/3 203 3/4 205 1 107 1-1/2 105
1/4 183 1/4 185 1/4 90 1/3 188 1/3 191 1/3 95 1/3 212 1/3 203 3/4 205 1 107 1-1/2 105
1/4 195 1/4 186 1/4 92 1/3 189 1/3 197 1/3 96 1/3 213 1/3 204 3/4 205 1 107 1-1/2 180
1/3 1 1/3 185 1/3 90 1/3 202 1/3 95 1/2 96 1/3 102 1/2 204 1 205 1-1/2 105
1/3 1 1/3 185 1/3 90 1/3 202 1/3 95 1/2 96 1/3 102 1/2 204 1 205 1-1/2 105
1/3 1 1/3 185 1/3 90 1/3 202 1/3 95 1/2 96 1/3 102 1/2 204 1 205 1-1/2 105 2 210
1/3 1 1/3 185 1/3 90 1/3 202 1/3 95 1/2 96 1/3 102 1/2 204 1 205 1-1/2 105 2 210
1/3 61 1/3 186 1/3 92 1/3 211 1/3 96 1/2 96 1/3 101 1/2 204 1 205 1-1/2 180 2 210
1/2 61 1/2 186 1/2 92 1/2 211 1/2 96 3/4 192 1/2 101 3/4 205 1-1/2 106 1-1/2 100
1/2 61 1/2 186 1/2 92 1/2 211 1/2 96 3/4 192 1/2 101 3/4 205 1-1/2 106 1-1/2 100
1/2 61 1/2 186 1/2 92 1/2 211 1/2 96 3/4 192 1/2 101 3/4 205 1-1/2 106 1-1/2 100 3 111
1/2 61 1/2 186 1/2 92 1/2 211 1/2 96 3/4 192 1/2 101 3/4 205 1-1/2 106 1-1/2 100 3 111
1/2 61 1/2 186 1/2 92 1/2 211 1/2 96 3/4 192 1/2 101 3/4 205 1-1/2 108 1-1/2 210 3 111
3/4 61 1/2 187 1/2 91 3/4 199 3/4 38 1 192 3/4 16 1 205
3/4 61 1/2 187 1/2 91 3/4 199 3/4 38 1 192 3/4 16 1 205
3/4 61 1/2 187 1/2 91 3/4 199 3/4 38 1 192 3/4 16 1 205 2 108 2 210 5 207
3/4 61 1/2 187 1/2 91 3/4 199 3/4 38 1 192 3/4 16 1 205 2 108 2 210 5 207
3/4 61 1/2 187 1/2 91 3/4 199 3/4 38 1 192 3/4 16 1 205 2 108 2 210 5 207
3/4 187 3/4 91 1 190 1 38 1-1/2 193 1 16 1-1/2 105
3/4 187 3/4 91 1 190 1 38 1-1/2 193 1 16 1-1/2 105
3/4 187 3/4 91 1 190 1 38 1-1/2 193 1 16 1-1/2 105 3 111 3 111
3/4 187 3/4 91 1 190 1 38 1-1/2 193 1 16 1-1/2 105 3 111 3 111
3/4 187 3/4 91 1 190 1 38 1-1/2 198 1 16 1-1/2 180 3 111 3 111
1 91 1 91 1-1/2 201 1-1/2 105
1 91 1 91 1-1/2 201 1-1/2 105
1 91 1 91 1-1/2 201 2 80 1-1/2 105 2 108 5 207
1 91 1 91 1- 1/2 201 2 80 1-1/2 105 2 108 5 207
1 91 1 91 1-1/2 209 2 80 1-1/2 180 2 108 5 207
25
Voltage 115/60/1 230/60/1 200/60/3 230/460/60/3
Mtr. Mtr. Total Total Mtr. Mtr. Total Total Mtr. Mtr. Total Total Mtr. Mtr. Total Total
HP Amps Rpm Amps Watts Amps Rpm Amps Watts Amps Rpm Amps Watts Amps Rpm Amps Watts
1/40
1.0 1550 1.3 110 0.4 1550 0.6 110
1/12
1.6 1625 1.9 200
1
/8
2.3 1625 2.6 300 1.0 1725 1.2 300
1/6
2.8 1075 3.1 310 1.5 1075 1.7 310
1/4
1.3 1725 1.7 380 1.3/.7 1725 1.6/0.8 380
1
/3
5.4 1075 5.7 490 2.2 1075 2.8 490 1.9 1140 2.1 490 2.1/1.1 1140 2.4/1.2 490
1/2
7.5 1075 7.8 690 3.5 1075 3.7 690 2.4 1140 2.8 740 2.6/1.3 1140 3.2/1.6 740
3/4
8.0 1125 8.3 840 4.0 1125 4.2 840 3.6 1140 3.8 1040 3.4/1.7 1140 3.6/1.8 1040
Pwr. Electric PD 30 PD 50 PD 75 PD 100 PD 125 PD 150 PD 175 PD 200 PD 250 PD 300 PD 350 PD 400
Code Power Horsepower
01
115/60/1 1/40 1/40 1/12 1/12 1/8 1/8 1/6 1/6 1/3 1/2 3/4 3/4
02
230/60/1 1/40 1/40 1/8 1/8 1/8 1/8 1/6 1/6 1/3 1/2 3/4 3/4
04
200/60/3 1/4 1/4 1/4 1/4 1/3 1/3 1/3 1/2 3/4 3/4
0
5
230/460/60/3
1/4 1/4 1/4 1/4 1/3 1/3 1/3 1/2 3/4 3/4
MOTOR DATA
P
ower Code Description Propeller PD Models
Motor Data and Total Unit Power Requirements Propeller PD Models
Power Code Description — Blower BD Models
Whenever 200V/1φ, 230V/1φ, 200V3φ, or 230V/3φ is used, it is necessary to specify 200V/230V controls. Whenever 460V (or 575V) 3φ power is used, it is
necessary to choose between 200V/230V or 460V (or 575V) controls. The 200V/230V controls will require the installer to provide a 460V (or 575V) to 230V (or
200V), 75VA step-down transformer [if the power exhauster accessory is used, the step-down transformer needs to be 250VA] with the motor starter coil voltage
being 230V (or 200V). The 460V (or 575V) controls require no additional transformer (unless the power exhauster accessory is used, then a 460V (or 575V) to 230V,
250VA step-down transformer is needed) with the motor starter coil voltage 24V.
PD units with 460V/3φ power supply are not listed by C.G.A.
All motors used are produced, rated and tested by reputable manufacturers in accordance with NEMA standards and carry the standard warranty of both the motor
manufacturer and Modine. All motors are totally enclosed and all single phase motors have built-in thermal overload protection.
BD50 BD75 BD100 BD125 BD150 BD175 BD200 BD250 BD300 BD350 BD400
Heater Parts from ACF Greenhouses