Product Brochure

9
6-175.7
BLOWER PERFORMANCE DATA - MODEL BTS
Table 9.1 - Power Code Description - Blower Model BTS M
M For selection of correct Power Code, refer to the Tables on pages 10-11.
Table 9.2 - Filter Static Pressure Drop N
BTS150 BTS175 BTS200 BTS250 BTS300 BTS350 BTS400
Filter Static (“W.C.) 0.1 0.2 0.1 0.2 0.2 0.2 0.2
N For blower units with enclosure and filter, add the following static pressures to the static pressure determined by the system designer for total
external static pressure.
BTS150 BTS175 BTS200 BTS250 BTS300 BTS350 BTS400
Power
Code Voltage Phase HP Drive HP Drive HP Drive HP Drive HP Drive HP Drive HP Drive
01 115 11/4230------------
02 115/230 1 1/3 230 1/3 238 1/2 233 1/2 204 1 240 1 1/2 250 1 1/2 247
08 208-230/460 3 1/3 230 1/3 238 1/2 233 1/2 204 1 257 1 1/2 251 1 1/2 248
11 575 3 1/3 231 1/3 239 1/2 233 1/2 204 1 257 1 1/2 251 1 1/2 248
13 115/230 1 1/3 232 1/2 229 1 229 1 241 1 241 1 1/2 247 - -
19 208-230/460 3 1/3 232 1/2 229 1 259 1 258 1 258 1 1/2 248 2 177
22 575 3 1/3 233 1/2 229 1 259 1 258 1 258 1 1/2 248 2 177
24 115/230 1 1/2 229 1 175 1 175 1.5 23 1 1/2 243 1 1/2 252 - -
30 208-230/460 3 1/2 229 1 253 1 253 1.5 177 1 1/2 244 1 1/2 180 3 246
33 575 3 1/2 229 1 253 1 253 1.5 177 1 1/2 244 1 1/2 180 3 246
35 115/230 1 1 175 1 1/2 237 1 1/2 235 - - 1 1/2 23 - - - -
41 208-230/460 3 1 253 1 1/2 234 1 1/2 236 2 180 1 1/2 177 2 177 5 245
44 575 3 1 253 1 1/2 234 1 1/2 236 2 180 1 1/2 177 2 177 5 245
52 208-230/460 3 - - - - - - - - 2 177 2 180 - -
55 575 3 - - - - - - - - 2 177 2 180 - -
63 208-230/460 3 - - - - - - - - 3 112 3 246 - -
66 575 3 - - - - - - - - 3 112 3 246 - -
74 208-230/460 3 - - - - - - - - - - 5 245 - -
77 575 3----------5245--