Full Product Manual

IHR Series Manual
10 11
Model
& Input
Type of Area
(Surroundings)
Approx.
Area
Covered
Approx.
Coverage
(sq. ft.)
Recommended
Mounting Height
Stnd. Reflector
(Dim. A)
Distance
Behind
Person or
Work Station
(Dim. B)
Centers for
Full Coverage
(Spot & Area)
Htg. Only
IHR 30
30,000
BTU/h
Cold/Drafty 10 x 10 100 9’ to 10’ 4’ 10
Average 12 x 12 144 10’ to 12 5’ 12
Protected/Insul. 14 x 14 196 12’ to 14’ 6’ 14
IHR 60
60,000
BTU/h
Cold/Drafty 16 x 16 256 12’ to 14’ 6’ 16
Average 18 x 18 324 14’ to 16 7’ 18
Protected/Insul. 20’ x 20 400 16’ to 18’ 8’ 20’
IHR 90
90,000
BTU/h
Cold/Drafty 20’ x 20’ 400 16’ to 18’ 9’ 20’
Average 24’ x 24’ 576 18’ to 20’ 10 24’
Protected/Insul. 28’ x 28 784 20’ to 22’ 11 26’
IHR 130
130,000
BTU/h
Cold/Drafty 26’ x 26’ 676 18’ to 20’ 11 26’
Average 30’ x 30’ 900 18’ to 20’ 12 28’
Protected/Insul. 35’ x 35’ 1225 20’ to 22’ 13 32’
IHR 160
160,000
BTU/h
Cold/Drafty 28’ x 28’ 784 20’ to 22’ 12 28’
Average 35’ x 35’ 1225 24’ to 26’ 16 32’
Protected/Insul. 40’ x 40’ 1600 28’ to 30’ 20’ 35’
Chart 2.2 • Recommended Mounting Heights and Distances for “Spot” Heating
2.0 Installation Heater Placement
A
B
Figure 2.2 Spot Heater Heights