User manual

3.0 INSTALLATION INSTRUCTIONS
MORNINGSTAR CORPORATION 13
Communication – Meter / MODBUS®
Choose the desired communication protocol for the RJ-11
meter connection. Select the Meter protocol to communicate
with a Morningstar Remote Meter (optional accessory).
Select the MODBUS® protocol to communicate with
a PC
2
and Morningstars MSView software. MODBUS®
is an open communication protocol standard used by
Morningstars MSView PC software and other 3rd party
hardware / software.
SWITCH 4 OFF (↓): MORNINGSTAR REMOTE METER
SWITCH 4 ON (↑): MODBUS® PROTOCOL FOR
MSVIEW, 3RD PARTY DEVICES
(2) Morningstar PC Meterbus Adapter (Model: MSC) required. Not included.
See Morningstars website for more information. www.morningstarcorp.com.
MODBUS® is a registered trademark of Modbus-IDA (www.modbus-ida.org)
3.0
3.3 Mounting
NOTE: When mounting the SunSaver MPPT, ensure free
air ow through the controller heat sink ns. There
should be at least 6 inches (150 mm) of clearance above
and below the controller to allow for cooling. If mounted
in an enclosure, ventilation is highly recommended.
WARNING: Risk of explosion! Never install the SunSaver
MPPT in a sealed enclosure with vented (ooded)
batteries! Do not install in a conned area where battery
gasses can accumulate.
Step 1: Choose Mounting Location
Locate the SunSaver MPPT on a vertical surface
protected from direct sun, high temperatures, and water.
Step 2: Check for Clearance
Place the SunSaver MPPT in the location where it will be
mounted. Verify that there is sufcient room to run wires and
that there is ample room above and below the controller for
air ow.
WARM AIR
COOL AIR
AT LEAST
6” (150 mm)
AT LEAST
6” (150 mm)
Figure 3. Mounting and cooling