Product Manual

E12
Installation instructions and Owner’s Manual
CHAPTER IV
OPERATOR MAINTENANCE
INSTRUCTIONS
1. TROUBLESHOOTING
A. Table 4 lists the common malfunctions which you
may nd during the operation or maintenance of your
heater.
B. For additional information, refer to Honeywell Field
Bulletin enclosed in the heater carton.
C. In the event results cannot be obtained after
performing all listed solutions, call the factory.
2. ADJUSTING THE PILOT FLAME
The pilot ame should envelop 3/8 to 1/2 in. (10 to
13 mm) of the tip of the thermocouple or generator.
Refer to Figure 11. To adjust:
MANUAL GAS
CONTROL KNOB
WRENCH
BOSS
GAS
INLET
PILOTSTAT POW-
ER UNIT
PRESSURE REGULATOR ADJUSTMENT
(BENEATH COVER SCREW)
PILOT FLOW ADJUSTING SCREW
(BENEATH COVER SCREW)
INSTALL LONG
SCREW IN
OUTSIDE CORNER
PILOT GAS OUTLET
(PRESSURE TAPPING
DIRECTLY BENEATH)
STANDARD
PRESSURE
REGULATOR
(“A” MODEL)
STEP OPENING REGULATOR
(“C” MODEL)
Figure 12. Top View of Standard Capacity Gas Control
3/8 TO 1/2 INCH
(10-13 MILLIMETERS)
THERMOCOUPLE
PROPER FLAME
ADJUSTMENT
Figure 11. Proper Flame Adjustment
A. Remove pilot adjustment cover screw. Refer to
Figure 12.
B. Turn inner adjustment screw clockwise to
decrease or counterclockwise to increase
pilot ame.
C. Always replace cover screw after adjustment and
tighten rmly to ensure proper operation.