Installation Summary - Indoor Unit
CAUTION
To prevent wall damage, use a stud finder to
locate studs.
A minimum pipe run of 9.8 ft (3 m) is required
to minimise vibration & excessive noise.
Two of the A, B, and C air circulation pathways
must be free from obstructions at all times.
This illustration is for demonstration
purposes only.
The actual shape of your air condtioner may
vary from the illustration.
Safety Precautions
1
2
3
4
1
Installation plate
Mounting screw
ST3.9
×25-C-H
Clip anchor
(1)
Remote
controller
holder
4 3
2
Air-break Switch
Drainage
Pipe
Air-break
Switch
Outdoor Unit
Power Cable
4
Installation Diagram
NOTE:
27K BTU 3 Zone DIY Multi-Zone Condenser
The combined linear length of all line-sets shall not
exceed 197 ft. The linear length of any single line-set
shall not exceed 75 ft. The laterial length between the
outdoor unit and any indoor unit shall not exceed 49 ft.
The laterial length between the lowest indoor unit and
the highest indoor unit shall not exceed 33 ft.
36K BTU 4 Zone DIY Multi-Zone Condenser
The combined linear length of all line-sets shall not
exceed 262 ft. The linear length of any single line-set
shall not exceed 75 ft. The lateral length between the
outdoor unit and any indoor unit shall not exceed 49 ft.
The lateral length between the lowest indoor unit and
the highest indoor unit shall not exceed 33 ft.
One-Two
One-Three
One-Four
More than
24in (60cm)
More than
24in (60cm)
More than
12 in (30cm)
More than
79in (200cm)
More than
12 in (30cm)
More than
4.7 in (12 cm)
More than 6 in
(15 cm)
More than
4.7 in (12 cm)
More than
4.7 in (12 cm)