- Power Measurement Modem User's Guide

Network Setup ION 7500 / ION 7600 User’s Guide
Page 36 Chapter 2 - Using The Front Panel
Network Setup
This menu item allows you to configure the Ethernet communications channel.
The following settings can be configured in this option:
Network settings can be configured automatically with BootP or manually
through the front panel. (You can also configure network settings via Designer or
ION Setup software — see “Using ION Software” on page 87 of this manual for
more information.)
Configuring Network Settings with BootP
The BootP network setting is enabled by default. When a BootP server is set up
with the correct information, the network settings (IP Address, Subnet Mask,
Gateway, and SMTP Mail Server IP Address) automatically configure.
Ask your Network Administrator whether a BootP server has been set up on your
network. If it has, and your Network Administrator has allocated the required
network settings on the BootP server, then all of the network settings (that your
facility requires) automatically appear on the Network Setup screen.
Setting Description Default
IP BootP
Option
A BootP server automatically sets the IP Address,
Subnet Mask, Gateway, and SMTP Mail Server IP
Address
– see your Network Administrator to determine if BootP
is used
If the IP BootP Option is set to BootP mode, then no
network settings can be changed
BootP
(Only meter’s ordered with the Ethernet option are set to BootP by
default; the default is otherwise set to Manual.)
IP Address Sets the IP Address for the meter
If a BootP server has been correctly set up, the IP Address number
appears.
If no BootP server has been set up (e.g. you wish to configure
settings through the front panel) then the default is None.
Subnet Mask
Used if subnetting applies to your network
– see your Network Administrator to determine if
Subnet Mask is used
If a BootP server has been correctly set up, and Subnet Mask is
used, then the Subnet Mask address number appears. If Subnet
Mask is not used, then the default is None.
If no BootP server has been set up (e.g. you wish to configure
through the front panel) then the default is None.
Gateway
Used in multiple network configurations
– see your Network Administrator to determine if
Gateway is used
If a BootP server has been correctly set up, and Gateway is used,
then the Gateway address number appears. If Gateway is not
used, then the default is None.
If no BootP server has been set up (e.g. you wish to configure
through the front panel) then the default is None.
SMTP
Address
Sets the IP Address for the SMTP Mail Server that is
configured to forward mail from the meter to the final
destination
– see your Network Administrator to determine if the
SMTP Mail Server is used
If a BootP server has been correctly set up, and an SMTP Address is
used, then the SMTP Address address number appears. If an SMTP
Address is not used, then the default is None.
If no BootP server has been set up (e.g. you wish to configure
through the front panel) then the default is None.