User Manual Network Module FP-1000, FP-1001

Chapter 2 Installation and Configuration
©
National Instruments Corporation 2-3 FieldPoint FP-1000/FP-1001 User Manual
3. Attach the terminal base to the network module by firmly mating
the local bus connectors.
4. To add more terminal bases, install them on the rail and mate their
local bus connectors together.
5. Place the protective cover that you removed from the network
module on the last terminal base on the bank, as shown in
Figure 2-4.
Figure 2-4. Connecting Terminal Bases
Connecting the FP-1000 to the Network
This section describes the network configurations possible with the
FP-1000 FieldPoint network module. The connector pinouts are
described in the RS-232 Interface Specifications and RS-485 Interface
Specifications sections later in this chapter.
Connect the RS-232 port of the FP-1000 to your host computer’s
RS-232 port. Use a 9-pin Dsub male-to-female “straight-through”
cable. Do not use a null modem cable (usually female-to-female).
You can connect only one FP-1000 network module for each RS-232
port in your host computer. You can add more FieldPoint banks without
using more RS-232 ports of your host computer, by connecting one or
more (up to 24) FP-1001 network modules to the RS-485 repeater port
of the FP-1000. This network configuration is shown in Figure 2-5.
Protective
Cover
Local Bus Connectors
Firmly Mated
Rail Snap
Locked
DIN
Rail