Digital Output Module Operating Instructions and Specifications

NI 9476 Operating Instructions and Specifications 4 ni.com
Caution Substitution of components may impair
suitability for Class I, Division 2.
Caution For Zone 2 applications, install the system
in an enclosure rated to at least IP 54 as defined by
IEC 60529 and EN 60529.
Caution For Zone 2 applications, install a protection
device between the external power supply and the V
sup
pin. The device must prevent the V
sup
-to-COM voltage
from exceeding 50 V if there is a transient overvoltage
condition.
Special Conditions for Hazardous Locations Use in Europe
This equipment has been evaluated as EEx nC IIC T4 equipment
under DEMKO Certificate No. 03 ATEX 0324020X. Each module
is marked II 3G and is suitable for use in Zone 2 hazardous
locations. If you are using the NI 9476 in Gas Group IIC hazardous
locations or in ambient temperatures of –40 °C Ta 70 °C, you
must use the device in an NI chassis that has been evaluated as
EEx nC IIC T4, Ex nA IIC T4, or Ex nL IIC T4 equipment.