User's Manual

NDA-24300 CHAPTER 4
Page 263
Issue 1
UNIT/CIRCUIT CARD REPLACEMENT PROCEDURE
1.3.4 Power Supply Unit Replacement Procedure
ATTENTION
Contents
Static Sensitive
Handling
Precautions Required
CPU System
Changeover
Refer to Section 12.1.2
in Chapter 6.
Cable to be disconnected from OUTPWR
CPU #0: 6P-(4P-3P) PWR CA-A
CPU #1: 6P-(4P-3P) PWR CA-B
START
Set the mode of the PWR UNIT (PZ-PW92)
to be replaced into STBY mode.
On the EMA (PH-PC40) card, set EMA SUP
switch UP.
Turn OFF the SW key on the PWR UNIT.
Disconnect the power cables from the OUTPWR
connector and INPWR connector on the PZ-PW92.
A
Disconnect the power alarm cable from the
PALM connector on the PZ-PW92.
Cable Name to be disconnected
CPU #0: 10AL-(110) FLT CA
CPU #1: 10AL-(130) FLT CA
Cable to be disconnected from INPWR
CPU #0: 4P-2P PWR CA-A
CPU #1: 4P-2P PWR CA-B
PWR (PZ-PW92)
FRONT VIEW
SW
ON
OFF
PALM
-48V
ON
ALM
OUTPWR
INPWR