ROUTINE MAINTENANCE PROCEDURE
2.8 Main Power System Check
Note:
For a longer battery life, observe the following items:
Place the batteries in a dark, cool place.
Keep the room temperature within the range of 10°C to 35°C (40°F to 85°F).
Floating voltage must be kept within the range of the battery specification at all times.
After discharging, perform equalized charging as per the battery specification.
Check the load voltage (DC 48V ±5 V) of the rectifier.
Check the batteries. Check the forced-charge voltage and floating
voltage.
Check the specific gravity, liquid level and
rated capacity of each battery.