09/12 Rev. B 143573
32
Parameter
Description
Default
(BCF...)
Default
(BC...)
min MAX
POSITIVE QUICK COOLING
P01
Room SetPoint in pos. quick cooling, Soft phase
23°F
23°F
-22°F
86°F
P02
SetPoint in pos. quick cooling, Hard
-12°F
-12°F
-40°F
86°F
P03
Needle SetPoint in pos. quick cooling , Soft phase
37°F
37°F
-22°F
86°F
P04
Needle SetPoint in Hard quick cooling
68°F
68°F
-22°F
86°F
P05
Positive quick cooling duration
90min
90min
0min
900min
P06
Hard phase duration expressed as % in relation to P05
60%
60%
0%
100%
P07
Room SetPoint in pos. storing
36°F
36°F
-22°F
86°F
NEGATIVE QUICK COOLING
N01
Room SetPoint in neg, quick cooling
-12°F
-12°F
-40°F
86°F
N02
Needle SetPoint in neg. quick cooling
0°F
-0°F
-22°F
86°F
N03
Negative quick cooling duration
240min
240min
0min
900min
N04
Room SetPoint in neg. storing
-7°F
-7°F
-40°F
86°F
ALARMS
A01
Temperature alarm hysteresis
4°F
4°F
0°F
18°F
A02
High temperature limit alarm in pos. storing in relation to P07
18°F
18°F
0°F
90°F
A03
Low temperature limit alarm in pos. storing in relation to P07
-17°F
-17°F
-90°F
0°F
A04
High temperature limit alarm in neg. storing in relation to N04
18°F
18°F
0°F
90°F
A05
Low temperature limit alarm in neg. storing in relation to N04
-17°F
-17°F
-90°F
0°F
A06
Temperature alarm delay fron storing or defrost start
60min
60min
0min
300min
A07
Temperature alarm delay
30min
30min
0min
300min
A08
Duration of the buzzer in the alarm mode
1min
1min
0min
240min
DISPLAY
D01
Temperature unit of measurement (0 Celsius; 1 Fahrenheit)
1
1
0
1
D02
Room probe Offset
0°F
0°F
-18°F
18°F
D03
BackLight (0 on when pressing a key; 1 always on)
0
0
0
1
D04
Core probe offset
0°F
0°F
-18°F
18°F
D05
Under surface probe offset
0°F
0°F
-18°F
18°F
D06
Over surface probe offset
0°F
0°F
-18°F
18°F
DEFROST
S01
Performs defrost on quick cooling start
0 = No; 1 = Yes
0
0
0
1
S02
End-of-defrost temperature
46°F
46°F
14°F
86°F
S03
Defrost max. duration
15 min
15 min
1 min
90 min
S04
Interval between defrosts in storing (0=excluded)
0 hour
0 hour
0
18 hour
S05
Type of defrost:
0= electrical or due to compressor stop
1= hot gas
2= air
2
2
0
2
S06
Dripping time
1 min
1 min
0 min
90 min
S07
Compressor activation delay with hot gas defrost
0 sec
0 sec
0 sec
600 sec
S08
First defrost activation time from storing start (0=excluded)
0
0
0
90 min
S09
Ignores compressor protection delays in defrost
0
0
0
1
S10
Defrost type started through keyboard:
0= electrical or due to compressor stop
1= hot gas
2= air
2
0
0
2
SERVICE
PARAMETERS
DESCRIPTION OF PARAMETERS