Manual

4.1 Configuration of the input signal
- Turn the device on and wait until it completed its built-in segment test.
- Press button 2 for 1 second, in the device display appears dP’ (decimal point).
- Select the desired decimal point place by pressing button 2 respective button 3.
- Validate the selected value by pressing button 1. The display shows dPagain.
- Press button 1 again, the display will show “ di.Lo“ (Display Low = low display value).
- Use button 2 and button 3 to select the desired value the device should display when a 4mA
resp. 0V input signa
l i
s attached.
- Validate the selected value by pressing button 1. The display shows di.Loagain.
- Press button 1 again, the display will show “ di.Hi“ (Display High = high display value).
- Use button 2 and button 3 to select the desired value the device should display when a 20mA
resp. 10V input signal is attached.
- Validate the selected value by pressing button 1. The display shows “ di.Hiagain.
- Press button 1 again. The display will show Li“ (Limit = Measuring range limit).
- Use button 2 and button 3 t
o s
elect the desired measuring range limit.
Display
Measuring range limit
Notes
off
Deactivated
Exceeding of the measuring range limit is
tolerable as of the measuring limit (p.r.t. hint).
on.Er
(on error)
Active, (displays error)
The meas. range limit is exactly bounded by
the input signal. When exceeding or
shortfalling the input signal an error message
will be displayed.
on.rG
(on range)
Active, (displays the
selected limit)
The meas. range limit is exactly bounded by
the input signal. When exceeding or short
falling the input signal the device will display
the selected lower/upper display value.
[e.g. humidity: when short falling or
exceeding, the device will display 0%
or 100%]
Hint:
When exceeding the measuring limit independently from the setting, the device will always
display an error message (“Err.1“ or “Err.2“).
The measuring limit is by 3.7 and 20.8 mA respective. 10.5 V (falling bellow 0V will not be
detected).
Button2
Button1
Button3
1010 West Bagley Road, Berea, Ohio 44017 P 440.243.0888 F 440.243.3472 www.noshok.com