Medium Voltage Power Cable
Product Construction
Conductor:
Annealed bare copper
Compact, Class B stranding
Extruded Strand Shield:
Extruded thermoset semi-conducng stress-control layer over
conductor
Insulaon:
Ethylene Propylene Rubber (EPR), colored to contrast with the
black conducng shield layers
Extruded Insulaon Shield:
Thermoset semi-conducng polymeric layer free stripping
from insulaon
Grounding Conductor(s):
1-3 bare or covered grounding conductors may be supplied in
the twisted assembly upon request
Metallic Shield:
Annealed copper tape with an overlap of 25%
Jacket:
Flame-retardant, moisture, and sunlight resistant Polyvinyl
Chloride (PVC)
Applications
Suitable for use in a broad range of commercial, industrial,
and ulity applicaons, where reliability is the major concern,
space is limited, and ease of installaon is crical
Suitable for use in wet or dry locaons when installed in
accordance with NEC
For use in aerial, direct burial, conduit, open tray, and
underground duct installaons
Features
UL Listed as Type MV-105 for use in accordance with the NEC
UL Labeled and marked “Sunlight resistant for CT Use”
Compact twisted assembly oers ease of installaon and lower
voltage drop characteriscs as compared to mulple single
conductor systems
Temperature Range: Normal 105°C, Emergency 140°C, Short
Circuit 250°C
Standards
Naonal Electric Code (NEC)
UL 1072
UL listed as Type MV-105 for use in accordance with NEC
IEEE 1202
OSHA Acceptable