2. Removing Wires from the Terminal
Use the following procedure to remove wires from the terminal.
The same method is used to remove stranded wires, solid wires, and
ferrules.
1. Hold a flat-blade screwdriver at an angle and insert it into the
release hole.
2. With the flat-blade screwdriver still inserted into the release hole,
remove the wire from the terminal insertion hole.
3. Remove the flat-blade screwdriver from the release hole.
3. Recommended Ferrules and Crimp Tools
Recommended ferrules
Note: 1. Make sure that the outer diameter of the wire is smaller than
the inner diameter of the insulating sleeve of the
recommended ferrule.
2. Make sure that the ferrule processing dimensions conform
to the following figure.
Recommended Flat-blade Screwdriver
Use a flat-blade screwdriver to connect and remove wires.
Use the following flat-blade screwdriver.
The following table shows manufacturers and models as of 2015/Dec.
Fuses
Use a quick-burning fuse on the output terminals to prevent
accidents due to short-circuiting. Use a fuse with equal or greater
performance than those given in the following table.
Recommended Fuse Capacity
EMC Ditective Compliance
EMC direcives can be complied with under the following conditions.
1. The G3PJ with Rated Load Voltage of 24 to 240 VAC (2@@B
model)
A capacitor must be connected to the load power supply.
The input cable must be less than 3 m.
2. The G3PJ with Rated Load Voltage of 100 to 480 VAC (5@@B
model)
A capacitor must be connected to the input power supply.
A capacitor, varistor and toroidal core must be connected to the
load power supply.
The input cable must be less than 3 m.
Applicable
wire
Ferrule
Conduct
length
(mm)
Recommended ferrules
(mm
2
)
(AWG)
Phoenix Contact
product
Weidmuller
product
Wago product
0.25 24 8 AI0.25-8 H0.25/12
FE-0.25-8N-YE
0.34 22 8 AI0.34-8 H0.34/12
FE-0.34-8N-TQ
0.5 20 8 AI0.5-8 H0.5/14
FE-0.5-8N-WH
0.75 18 8 AI0.75-8
H0.75/14 FE-0.75-8N-GY
1 18 8 AI1-8 H1.0/14
FE-1.0-8N-RD
1.5 16 8 AI1.5-8 H1.5/14
FE-1.5-8N-BK
Recommended crimp tool CRIMPFOX6 PZ6 roto Variocrimp4
Flat-blade screwdriver
1
10 to 15˚
Wire
2
3
8 mm
2.1 mm max.
2.7 mm max.
Model Manufacturer
XW4Z-00B Omron
ESD 0.402.5 Wera
SZF 0.42.5 Phoenix Contact
0.42.575 302 Wiha
AEF.2.575 Facom
210-719 Wago
*1
*1.
Insulated types of Flat-blade Screw driver, strongly recommended
to prevent from an electric shock.
SDI 0.42.575 Weidmuller
*1
98 20 25 KNIPEX
*1
Rated G3PJ output
current
Applicable SSR
Fuse
(IEC 60269-4)
15 A
G3PJ-
@
15B Series
32 A
25 A
G3PJ-
@
25B Series
Side
0.4 mm
2.5 mm dia.
2.5 mm
Front
LOAD
G3PJ
OUTPUT
INPUT
Recommended Capacitor (Film capacitor) : 1µF , 250VAC
3 m Max.
LOAD
G3PJ
OUTPUT
INPUT
Recommended Capacitor (Film capacitor) : 0.05µF , 500VAC (LOAD)
0.1µF , 250VAC (INPUT)
Recommended Varistor : 470V, 1750A
Recommended Troidal core : NEC/TOKIN:ESD-R-25B or equivalent
3 m Max.
Troidal core