Owner manual

Appendix 2 Toxic or Hazardous Materials or Elements Identification Table 47
47
Chapter 7 Product Specification
This chapter provides UPS product specification.
7.1 Applicable Standards
The UPS has been designed to conform to the following European and international standards:
Table 7-1 Compliance with European and International Standards
Item
Normative reference
General safety requirements for UPS
used in operator access areas
EN50091-1-1/IEC62040-1-1/AS 62040-1-1
Electromagnetic compatibility (EMC)
requirements for UPS
EN50091-2/IEC62040-2/AS 62040-2(C3)
Method of specifying the performance
and test requirements of UPS
EN50091-3/IEC62040-3/AS 62040-3(VFI SS 111)
Note: The above mentioned product standards incorporate relevant compliance clauses with generic
IEC and EN standards for safety (IEC/EN/AS60950), electromagnetic emission and immunity
(IEC/EN/ AS61000 series) and construction (IEC/EN/AS60146 series and 60950).
7.2 Environmental Characteristics
Table 7-2 Environmental Properties
Items
Unit
Requirements
Acoustic noise level at 1
meter
dB
55.0
Altitude of Operation
m
≤1000m above sea level, derate power by 1% per 100m
between 1000m and 2000m
Relative Humidity
RH
0 to 95%, non condensing
Operating Temperature
0 to 40 deg , Battery life is halved for every 10°C increase
above 20°C
UPS Storage-Transport
Temperature
20
70
Recommended Battery
Storage Temperature
20
30 (20°C for optimum battery storage)
7.3 Mechanical Characteristics
Table 7-3 Mechanical Properties
Cabinet Specification
Unit
MD60-10, MD90-15,
MD120-20
MD100-10, MD150-15,
MD200-20
Mechanical Dimension,
W×H
mm
600×900×1600
600×900×2000
Weight
kg
151
182
Color
N/A
Black
Protection Level,
IEC(60529)
N/A
IP20