7.6 Electrical Characteristics (Inverter Output)
Table 7-6 Inverter Output (to important load)
Rated
capacity(kVA)
Unit
10~200
Rated AC voltage
1
Vac
380/400/415(three-phase four-wire and sharing neutral with the
bypass)
Freqency
2
Hz
50/60
overload
%
105
%
load, 1 hour
110
%
load, 10min
125
%
load, 1min
150
%
load, 5sec
>
150
%
load, 200ms
Fault current
%
340
%
short current limitation for 200ms
Non linear load
capability
3
%
100
%
Neutral current
capability
%
170
%
Steady state
voltage stability
%
±1(balanced load)
±1.5(100
%
imbalance load)
Transient voltage
response
4
%
±5
THD
%
<
1.5(linear load) ,
<
5(non linear load
3
)
Synchronization -
Window
Rated frequency ±2Hz(selectable: ±1
~
±5Hz)
Max change rate of
synch frequency
Hz/s
1: selectable: 0.1
~
5
Inverter voltage
range
%
V(ac)
±5
Note:
1. Factory setting is 380V. Commissioning engineers can set to 400V or 415V.
2. Factory setting is 50Hz. Commissioning engineers can set to 60Hz.
3. EN50091-3(1.4.58) crest ratio is 3: 1.
4. IEC62040-3/EN50091-3 including 0
%~
100
%~
0
%
load transient, the recovery time is half
circle to within 5% of stable output voltage.