Appendix A Guidebook to Ordering and Selection of MD System
MD series UPS module can be divided into equipment cabinet and power module. For the cabinet
lectotype please refer to the description in fig 6-1.
Fig 6-1 Cabinet Selection
For single power module type please refers to the description in fig 6-2:
Fig 6-2 Power Module Selection
Egg: the requirements of a plant room are given below:
The maximum power supply of the plant room is 120kVA; however, it is expected to be expanded to
200kVA in 3-5 years. Therefore, a 200kVA cabinet and 6 20kVA power module can be purchased to
constitute an uninterrupted 120kVA power system which can be expanded to 200kVA on-line. The order
symbol is:
1 set MD200/20
6 set MU20
Option list:
MD-SNMP card: remote network monitoring card
MD-1600 dust filter: dust screen for 1.6m cabinet
MD-2000 dust filter: dust screen for 2m cabinet
Represents the capacity of a single power module
10 represents 10kVA
15 represents 15kVA
20 represents 20kVA
represents a single power module
Represents UPS system capacity/power module
60/10 represents 60kVA/10kVA
90/15 represents 90kVA/15kVA
120/20 represents 120kVA/20kVA
150/15 represents 150kVA/15kVA
200/20 represents 200kVA/20kVA