Owner manual

26 Chapter 2 Operations
26
2.2.6 ECO Mode
If economical (ECO) mode is selected, the double-conversion UPS will stop to work so as to save
energy. During the operation of ECO mode, the load power will be supplied by bypass preferentially.
When bypass power is within the range of normal frequency and voltage, load power will be supplied by
bypass, or the system will transfer to inverter output, followed by load power interruption which extends
within 3/4 of the utility period. E.g. when the frequency is 50Hz, the interruption time will be less than
15ms; when the frequency is 60Hz, the time will be less than 12.5ms.
2.2.7 Frequency Converters Mode
If the frequency converter configuration is used by UPS, it will provide 50Hz or 60Hz stable output
frequency. The range of output frequency is 40Hz70Hz. Under this mode, static bypass is unavailable,
but battery can be selected according to the actual requirements of battery mode.
2.3 Battery Management
2.3.1 Normal Function
The following functions should be fitted by commissioning engineers with specified software.
1. Constant current boost charging
Current can be set up.
2. Constant voltage boost charging
Voltage of boost charging can be set as required by the type of battery.
For Valve Regulated Lead Acid (VRLA) batteries, maximum boost charge voltage should not
exceed 2.4V / cell.
3. Float charge
Voltage of float charging can be set as required by the type of battery.
For VRLA, float charge voltage should be between 2.2V to 2.3V.
4. Float charge temperature compensation (optional)
A coefficient of temperature compensation can be set as required by the type of battery.
5. End of discharge (EOD) protection
If the battery voltage is lower than the EOD, the battery converter will shut down and the battery is
isolated to avoid further battery discharge. EOD is adjustable from 1.6V to 1.75V per cell (VRLA) or 0.9
to 1.1 V per cell
6. Battery low warning time
It is adjustable between 3 and 60 minutes. The default is 5 minutes.
2.3.2 Advanced Functions (Battery Self-checking and Maintenance)
At periodic intervals, 20% of the rated capacity of the battery will be discharged automatically, and
the actual load must exceed 20% of the rated UPS (KVA) capacity. If the load is less than 20%,
auto-discharge cannot be executed. The periodic interval can be set from 30 to 360 days. The battery
self-test can be disabled.
ConditionsBattery at float charge for at least 5 hours, load equal to 20~100% of rated UPS capacity
Trigger—Manually through the command of “Battery Maintenance Test” in LCD panel or automatically
Battery Self-Test Interval30-360 days (default setting is battery self-test disabled).