Outback Power VFX Series Installation Manual

12
DC
Use crimped and sealed copper ring terminal lugs with 5/16” (.79 cm) hole or compression-type lug
to connect battery cables to DC terminals. Soldered cable lugs are also acceptable.
Use recommended cable sizes (see page 51) to reduce losses and ensure high performance of FX
(smaller cables can reduce performance and possibly damage the unit).
Keep cables together (e.g., using a tie-wrap) as much as possible.
Ensure cables pass through the same knockout and conduit  ttings to allow inductive currents to
cancel.
TORQUE REQUIREMENTS
CONNECTION TORQUE IN POUNDS/Nm
AC and PV breakers to 22 inch-lbs/2.48 Nm
DC shunt to 15 foot-lbs/20.4 Nm
DC battery connections to 10 foot-lbs/13.6 Nm
FX’s DC terminals to 5 foot-lbs/3.38 Nm
FX’s AC terminals to 30 inch-lbs/3.38 Nm
Table 1 Torque Values for Installation